Plan Review Notes
Plan Review Notes For Permit 11110429
Permit Number 11110429
Review Stop B
Sequence Number 2
Notes
Date Text
2012-02-02 15:21:39PLANS WILL NOT BE STAMPED AT THIS TIME. NEW SHEETS WILL
 BE ADDED COMMENTS FROM FIRE. THE CONTRACTOR WILL NEED
 TO COLLATE PLANS INTO TWO SETS, PULL OUT ALL OLD SHEETS
 THAT HAVE BEEN SUPERCEDED.
  
 BUILDING PROVISO:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) ROOFING PRODUCT APPROVALS HAVE BEEN SUBMITTED BUT
 SUBSYSTEMS HAVE NOT BEEN HIGHLIGHTED, INHANCED
 FASTENING MAY BE REQUIRED ONCE SUBSYSTEM IS KNOWN.
  
 1A) NOA 09-1027.07
 CARLISLE SYNTEC INC.
 CARLISLE SURE-WELD SINGLE PLY TPO ROOF SYSTEMS OVER
 STEEL DECK
  
 1B) NOA 07-1023.09
 MONIER LIFETILE
 SPANISH "S" CONCRETE ROOF TILE
 PAGE 5-6 TYPE OF ATTACHMENT NOT CIRCLED, MOMENT UNKNOWN
  
 2) NEW ELEVATION CERTIFICATE WILL BE REQUIRED BEFORE
 ISSUANCE SECTION F UNDER COMMENTS THE HAG/ LAG ARE
 REVERSED.