| Date |
Text |
| 2011-11-30 13:29:11 | BUILDING PLAN REVIEW |
| | PERMIT: 11110429 |
| | ADD: 8289 OKEECHOBEE BLVD |
| | CONT: JACOB ERECTING & CONSTRUCTION |
| | TEL: (561)282-7441 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE THE MINIMUM FINISH SLAB ELEVATON ON |
| | PLANS NOT LOCATED ON SHEET A.1 OR S1.1.FBC BUILDING |
| | 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "AO" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED PROVIDING |
| | THE MINIMUM SLAB ELEVATION. |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | MARCH 31, 2012. |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012. |
| | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| | MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS |
| | NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES |
| | MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED |
| | ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW |
| | FORM. |
| | |
| | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 2) SOILS REPORT TO PROVIDE THE MINIMUM SAFE BEARING |
| | VALUE FOR THIS PROJECT. |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . |
| | |
| | 3) SHEET A.1 NOTED RESTROOM DOORS IN SERIES11-4.13.6. |
| | NO ACTION REQUIRED. THE USAGE OF RESTROOMS WILL BE FROM |
| | ONE CLASSROOM ONLY NOT FOR PASSAGE TROUGH RESTROOM. |
| | |
| | 4) SHEET A.1 LAUNDRY ROOM INDICATES TTHE USE OF 1-HOUR |
| | RATED WALLS, DETAIL "A" IS FOR A 1 HOUR RATED WALL WITH |
| | NOTE TO USE STA-SMOOTH FS-90 FIRE SHIELD COMPOUND, |
| | PLEASE NOTE THIS JOINT WILL NEED TO BE A FLEXABLE JOINT |
| | BECAUSE OF THE EXSPANSION & CONTRACTION BETWEEN |
| | DISSIMILAR MATERIALS (GYPSUM & ROOF METAL DECKING) AND |
| | BUILDING MOVEMENT. FBC-B 713.2 INSTALATION & FBC-B |
| | 713.3. |
| | |
| | 5) SHEET A.1 INDICATES UNDER THE HEADING OF STANDARD & |
| | NOTES THIS BUILDING IS TO BE "FIRE SPRINKLERED". THE |
| | AREA INCREASE SHOWN ON THIS PAGE ALSO INDICATES THIS |
| | BUILDING IS DESIGNED TO BE FIRE SPRINKLERED, BUT NO |
| | FIRE SPRINKLER PLANS WERE PROVIDED. FBC-B MINIMUM |
| | BUILDING PLAN REVIEW- COMMERCIAL BUILDINGS 106.3.5.1(5) |
| | SCHEMATIC FIRE SPRINKLERS. |
| | |
| | 6) SHEEET A.1 SUPPLY CLOSET # 1, SUPPLY CLOSET # 2 & |
| | SUPPLY CLOSET WILL NEED TO SHOW COMPLIANCE WITH FBC-B |
| | 436.6 PROTECTION FROM HAZARDS, AT THIS TIME IT IS |
| | UNKNOWN AS TO USAGE OF THESE ROOMS. |
| | |
| | 7) SHEET A3 ROOF PLAN THE WEST ELEVATION APPEARS TO |
| | HAVE LEFT OUT THE LOCATION OF TWO SCUPPER? 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 8) SHEET A1 & A3 BOTH SHOW DETAILS INDICATING THE USE |
| | OF FULCRUM POLYURETHANE CORNER PRODUCTS, PLEASE PROVIDE |
| | MANUFACTURERS SPEC SHEET ON FLAME SPREAD AND SMOKE |
| | DEVELOPMENT FBC-B 803.1 & TABLE TABLE 803.5. "C" CLASS |
| | FLAME SPREAD. |
| | |
| | 9) SHEET A5 THE GYM AREA INDICATES THE USE OF HI-HAT |
| | MATERIAL WITH 5/8 INCH GYPSUM DRYWALL, THE STRUCTURAL |
| | SHEET S1.2 INDICATES THE BAR JOIST SPACING @ 5'-0" OC |
| | THE LARGEST SPAN, PLEASE PROVIDE THE HEIGHT OF THE |
| | HI-HAT AND THICKNESS OF THE MATERIAL FOR THIS |
| | INSTALATION. SPANS FOR L/240? ADDITINAL INFORMATION |
| | REQUIRED 106.1.2. |
| | |
| | 10) MISSING PRODUCT APPROVALS. 106.3.3 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS INCLUDING BILCO HATCH. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOF TOP |
| | (DECK) INSULATION |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |