Plan Review Notes
Plan Review Notes For Permit 11110429
Permit Number 11110429
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-30 13:29:11BUILDING PLAN REVIEW
 PERMIT: 11110429
 ADD: 8289 OKEECHOBEE BLVD
 CONT: JACOB ERECTING & CONSTRUCTION
 TEL: (561)282-7441
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE MINIMUM FINISH SLAB ELEVATON ON
 PLANS NOT LOCATED ON SHEET A.1 OR S1.1.FBC BUILDING
 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "AO" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED PROVIDING
 THE MINIMUM SLAB ELEVATION.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SOILS REPORT TO PROVIDE THE MINIMUM SAFE BEARING
 VALUE FOR THIS PROJECT.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 3) SHEET A.1 NOTED RESTROOM DOORS IN SERIES11-4.13.6.
 NO ACTION REQUIRED. THE USAGE OF RESTROOMS WILL BE FROM
 ONE CLASSROOM ONLY NOT FOR PASSAGE TROUGH RESTROOM.
  
 4) SHEET A.1 LAUNDRY ROOM INDICATES TTHE USE OF 1-HOUR
 RATED WALLS, DETAIL "A" IS FOR A 1 HOUR RATED WALL WITH
 NOTE TO USE STA-SMOOTH FS-90 FIRE SHIELD COMPOUND,
 PLEASE NOTE THIS JOINT WILL NEED TO BE A FLEXABLE JOINT
 BECAUSE OF THE EXSPANSION & CONTRACTION BETWEEN
 DISSIMILAR MATERIALS (GYPSUM & ROOF METAL DECKING) AND
 BUILDING MOVEMENT. FBC-B 713.2 INSTALATION & FBC-B
 713.3.
  
 5) SHEET A.1 INDICATES UNDER THE HEADING OF STANDARD &
 NOTES THIS BUILDING IS TO BE "FIRE SPRINKLERED". THE
 AREA INCREASE SHOWN ON THIS PAGE ALSO INDICATES THIS
 BUILDING IS DESIGNED TO BE FIRE SPRINKLERED, BUT NO
 FIRE SPRINKLER PLANS WERE PROVIDED. FBC-B MINIMUM
 BUILDING PLAN REVIEW- COMMERCIAL BUILDINGS 106.3.5.1(5)
 SCHEMATIC FIRE SPRINKLERS.
  
 6) SHEEET A.1 SUPPLY CLOSET # 1, SUPPLY CLOSET # 2 &
 SUPPLY CLOSET WILL NEED TO SHOW COMPLIANCE WITH FBC-B
 436.6 PROTECTION FROM HAZARDS, AT THIS TIME IT IS
 UNKNOWN AS TO USAGE OF THESE ROOMS.
  
 7) SHEET A3 ROOF PLAN THE WEST ELEVATION APPEARS TO
 HAVE LEFT OUT THE LOCATION OF TWO SCUPPER? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) SHEET A1 & A3 BOTH SHOW DETAILS INDICATING THE USE
 OF FULCRUM POLYURETHANE CORNER PRODUCTS, PLEASE PROVIDE
 MANUFACTURERS SPEC SHEET ON FLAME SPREAD AND SMOKE
 DEVELOPMENT FBC-B 803.1 & TABLE TABLE 803.5. "C" CLASS
 FLAME SPREAD.
  
 9) SHEET A5 THE GYM AREA INDICATES THE USE OF HI-HAT
 MATERIAL WITH 5/8 INCH GYPSUM DRYWALL, THE STRUCTURAL
 SHEET S1.2 INDICATES THE BAR JOIST SPACING @ 5'-0" OC
 THE LARGEST SPAN, PLEASE PROVIDE THE HEIGHT OF THE
 HI-HAT AND THICKNESS OF THE MATERIAL FOR THIS
 INSTALATION. SPANS FOR L/240? ADDITINAL INFORMATION
 REQUIRED 106.1.2.
  
 10) MISSING PRODUCT APPROVALS. 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS INCLUDING BILCO HATCH.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOF TOP
 (DECK) INSULATION
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]