| 2011-12-14 15:16:05 | PLANS DENIED | | | 1) OCCUPANCY LOAD IS OVER 100 PEOPLE ENGINEER OR | | | ARCHITECT MUST DESIGN THE MECHANICAL SYSTEM. | | | 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS . | | | 3) PROVIDE A DETAIL ON THE CURB TO ROOF TIE DOWN AND | | | UNIT TO CURB TIE DOWN. | | | PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M) | | | 4) PROVIDE EQUIPMENT SCHEDULE ON PLANS. | | | 5) CHANGE VALUE OF THE JOB ON THE APPLICATION. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|