| 2011-12-16 12:43:45 | 330 CLEMATIS STREET - SUITE #117 |
| | PERMIT #11110361 |
| | ROUND 2 REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE MECHANICAL PLAN SUBMITTED IS NOT SIGNED OR SEALED |
| | BY THE ENGINEER AND THE ADDRESS DOES NOT MATCH THE |
| | PERMIT APPLICATION OR OTHER CONSTRUCTION DOCUMENTS. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE |
| | FIRESTOP DETAILS INDICATING THE MATERIALS AND METHODS |
| | USED TO MAINTAIN THE FIRE RATED LISTING OF THE WALL. |
| | |
| | MODIFICATIONS SHOWN ON THE PLANS WILL AFFECT THE |
| | EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEM. SEPARATE |
| | PLANS AND PERMITS ARE REQUIRED FOR THE MODIFICATION OF |
| | THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM. THE |
| | PLANS ONLY INDICATE ONE FIRE ALARM STROBE APPLIANCE. |
| | SPRINKLER SPACING INDICATES COVERAGES GREATER THAN 130 |
| | SQUARE FEET (THE MAXIMUM ALLOWED FOR ORDINARY HAZARD). |
| | NO SPRINKLER PROTECTION PROVIDED IN TWO RESTROOMS. |
| | SEVERAL SPRINKLERS LOCATED MORE THAN 7'-6" FROM WALLS. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |