Plan Review Notes
Plan Review Notes For Permit 11110361
Permit Number 11110361
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2011-12-16 12:43:45330 CLEMATIS STREET - SUITE #117
 PERMIT #11110361
 ROUND 2 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE MECHANICAL PLAN SUBMITTED IS NOT SIGNED OR SEALED
 BY THE ENGINEER AND THE ADDRESS DOES NOT MATCH THE
 PERMIT APPLICATION OR OTHER CONSTRUCTION DOCUMENTS.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 FIRESTOP DETAILS INDICATING THE MATERIALS AND METHODS
 USED TO MAINTAIN THE FIRE RATED LISTING OF THE WALL.
  
 MODIFICATIONS SHOWN ON THE PLANS WILL AFFECT THE
 EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEM. SEPARATE
 PLANS AND PERMITS ARE REQUIRED FOR THE MODIFICATION OF
 THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM. THE
 PLANS ONLY INDICATE ONE FIRE ALARM STROBE APPLIANCE.
 SPRINKLER SPACING INDICATES COVERAGES GREATER THAN 130
 SQUARE FEET (THE MAXIMUM ALLOWED FOR ORDINARY HAZARD).
 NO SPRINKLER PROTECTION PROVIDED IN TWO RESTROOMS.
 SEVERAL SPRINKLERS LOCATED MORE THAN 7'-6" FROM WALLS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW