| Plan Review Notes For Permit 11110361 |
| Permit Number |
11110361 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-12 14:57:48 | PLANS DENIED. | | | 1) PROVIDE THE LOCATION FOR THE CONDENSATE LINE ON THE | | | PLANS. | | | 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS. | | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR AND 606.3 | | | INSTALLATION. | | | 2007 FBC (M) | | | 4) REFER TO SECTION 606.4.1 SUPERVISION 2007 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|