2011-12-12 14:57:48PLANS DENIED.
 1) PROVIDE THE LOCATION FOR THE CONDENSATE LINE ON THE
 PLANS.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 3) REFER TO SECTION 606.2.1 SUPPLY AIR AND 606.3
 INSTALLATION.
 2007 FBC (M)
 4) REFER TO SECTION 606.4.1 SUPERVISION 2007 FBC (M)
 PLAN REVIEW BY HAROLD MOSER