| Plan Review Notes For Permit 11110361 |
| Permit Number |
11110361 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-11-29 09:13:29 | BUILDING PLAN REVIEW | | | PERMIT: 11110361 | | | ADD: 330 CLEMATIS ST SUITE 117 SEPERATE PERMIT FOR | | | SUITE #118 | | | CONT: MUNNA CONTRACTING & DEVELOPMENT | | | TEL: (561)371-7677 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) SHEET A-1 INDICATES WITH A NOTE DETAIL # 3 TO BE A | | | 1-HOUR TENANT SEPERATION WALL TO DECK ABOVE BUT THERE | | | IS NO SUCH DETAIL. | | | | | | 2) PLEASE PROVIDE THE FOLLOWING NOTATION ABOVE THE | | | CEILING ON RATED WALLS: "FIRE AND SMOKE BARRIER - | | | PROTECT ALL OPENINGS." 712.6 FIRE WALLS, FIRE BARRIERS, | | | FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR | | | ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS | | | SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDENTIFICATION | | | SHALL BE ABOVE ANY DECORATIVE CEILING AND IN CONCEALED | | | SPACES. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|