Plan Review Notes
Plan Review Notes For Permit 11110349
Permit Number 11110349
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-29 07:55:502007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE WIND DESIGN CRITERIA FOR THE DESIGN ON
 THE PLANS. SPECIFY WIND SPEED AND EXPOSURE CATEGORY.
 SEE FBC R 301.2.1.
  
 2) PROVIDE A BUCK FASTENING DETAIL FOR THE NEW FRENCH
 DOORS ON THE PLANS. SEE FBC R613.6.1.1
  
 3) REVISE GENERAL NOTE NUMBER 4 ON THE COVER SHEET TO
 REFERENCE THE CURRENT BUILDING CODE WHICH IS THE 2007
 FBC WITH 2009 REVISIONS.
  
 4) THE SOIL THAT IS REMOVED TO INSTALL THE NEW UNDER
 SLAB PLUMBING WILL BE REQUIRED TO BE TREATED FOR
 TERMITES IN ACCORDANCE WITH FBC R320.
  
 5) THE EXISTING WINDOW THAT WAS LOCATED IN THE BEDROOM
 AND AS A RESULT OF THE RECONFIGURATION OF THE FLOOR
 SPACE WILL NOW BE LOCATED IN THE MASTER BATH IS
 REQUIRED TO COMPLY WITH FBC R 308.4 (5) FOR GLAZING
 LOCATED IN HAZARDOUS LOCATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]