2011-11-29 15:50:491601 FORUM PLACE - SUITE #801
 PERMIT #11110322
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DOORS LOCATED IN ONE-HOUR FIRE RATED WALLS SHALL BE
 FIRE-RATED FOR 45 MINUTES.
  
 THE ELEVATOR LOBBY MAY NEED TO BE SEPARATED FROM
 ADJACENT BUILDING SPACE; REFER TO BUILDING DEPT REVIEW
 COMMENTS. NOTE:THE ORIGINAL DESIGN DOCUMENTS
 INCORPORATED A ROLLING FIRE SHUTTER IN THE ELEVATOR
 LOBBY.
  
 SHEET E-1: PROVIDE VISUAL NOTIFICATION APPLIANCE IN
 KITCHEN #101 AND FILES #104.
  
 SHEET E-1: CONFIRM VISUAL NOTIFICATION APPLIANCES ARE
 EXISTING IN THE MEN'S AND WOMEN'S RESTROOMS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  