Plan Review Notes
Plan Review Notes For Permit 11110322
Permit Number 11110322
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-28 12:01:30BUILDING PLAN REVIEW
 PERMIT: 11110322
 ADD: 1601 FORUM PLACE # 801
 CONT: FISHER CONSTRUCTION
 TEL: (561)691-4716
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE: THE DESIGNER OF RECORD HAS NOT INDICATED AS TO
 WHICH DESIGN METHOD UNDER THE FLORIDA EXISTING BUILDING
 CODE THIS PROJECT WAS DESIGNED TOO.
 . THE 2007/ 09 FLORIDA EXISTING BUILDING CODE ( EXST
 BLDG CODE) PROVIDES THE DESIGNER OF RECORD OPTIONS IN
 COMPLIANCE WITH RENOVATIONS, SEE EXST BLDG CODE 101.5.
 FOR THE PURPOSE OF THIS REVIEW
 THE WORK AREA METHOD WILL BE USED AND DEFINED AS A
 LEVEL II ALTERATION EXST BLDG CODE 404.1.
 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION
 OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
  
 1) THE PERMIT APPLICATION INDICATES THE SCOPE OF WORK
 IS FOR TENANT INTERIOR RENOVATIONS FOR SUITE # 801. A
 SECOND PERMIT NUMBER (11110602) WILL BE GENERATED FOR
 SUITE 805 FOR TENANT SEPARATION WALLS ONLY, FOR
 TRACKING AND INSPECTION PURPOSES.
  
 2) SHEET A-3 INDICATES MORE THAN 50% OF THE FLOOR AREA
 IS TO BE ALTERED. THIS LEADS US INTO REVIEWING FOR CODE
 COMPLIANCE FOR ELEVATOR LOBBIES. THE BUILDING OFFICIAL
 & BATTALION CHIEF HAVE ISSUED A MEMORANDUM IN REGARDS
 TO REMODELING OF FLOORS IN HIGH RISE BUILDINGS WHERE
 THE CODES HAVE REQUIRED ELEVATOR LOBBIES OR THEIR
 EXCEPTIONS SINCE 1929.
  
 TO BETTER PREPARE BUILDING OWNERS, MANGERS, OPERATORS,
 AND DESIGN PROFESSIONALS TO ANTICIPATE AND ADDRESS
 THESE SPECIFIC CODE REQUIREMENTS, THE CONSTRUCTION
 SERVICES DEPARTMENT AND FIRE PREVENTION DEPARTMENT
 PROPOSE TO ADDRESS THE ABSENCE OF AN ELEVATOR LOBBY
 (WHEN REQUIRED) AS FOLLOWS:
  
 1. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES
 TO RECONFIGURE THE ENTIRE EXISTING BUILDING FLOOR, AN
 ELEVATOR LOBBY, OR COMPLIANCE WITH ONE OF THE SIX (6)
 EXCEPTIONS ALLOWED UNDER THE PRESENT CODE WILL BE
 REQUIRED. THIS IS REGARDLESS OF WHETHER OR NOT THE
 ABSENCE OF AN ELEVATOR LOBBY CAN BE DEMONSTRATED WITH A
 VALID PERMIT ISSUED BETWEEN OCTOBER 1, 2005 AND
 DECEMBER 8, 2006.
 2. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES
 TO RECONFIGURE A PORTION OF THE EXISTING BUILDING FLOOR
 AREA, WITH NO WORK BEING PROPOSED IN THE AREA OF THE
 ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS FOUND TO EXIST
 ON THE FLOOR, AND A VALID PERMIT CAN BE EVIDENCED WHICH
 WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER 8,
 2006, THE TENANT IMPROVEMENT PERMIT MAY BE APPROVED AND
 THE BUILDING SHALL REMAIN AS LAWFULLY CONFIGURED UNTIL
 THE MAJORITY OF THE EXISTING FLOOR PLAN, OR THE
 ELEVATOR LOBBY AREA ITSELF UNDERGOES RENOVATION.
 3. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES
 TO RECONFIGURE A PORTION OF THE EXISTING BUILDING FLOOR
 AREA, WITH NO WORK BEING PROPOSED IN THE AREA OF THE
 ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS FOUND TO EXIST
 ON THE FLOOR, AND NO VALID PERMIT CAN BE EVIDENCED
 WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER
 8, 2006, THE TENANT IMPROVEMENT PERMIT MAY BE APPROVED.
 THE BUILDING OWNER WILL BE NOTIFIED OF AN UNSAFE
 CONDITION ON THE EXISTING STRUCTURE BY THE CITY FIRE
 MARSHAL?S OFFICE AND ASKED TO UNDERTAKE APPROPRIATE
 ACTIONS TO CORRECT THE SITUATION.
 4. IF ANY RECONFIGURATION IS PROPOSED WHICH AFFECTS THE
 ELEVATOR LOBBY AREA ITSELF, AN ELEVATOR LOBBY, OR
 COMPLIANCE WITH ONE OF THE SIX (6) EXCEPTIONS LISTED IN
 THE CODE SHALL BE REQUIRED.
  
 IT SHOULD BE NOTED THAT CITY STAFF REMAINS COMMITTED TO
 ASSISTING BUILDING OWNERS, MANAGERS, AND DESIGN
 PROFESSIONALS IN SUCCEEDING IN CREATING AND MAINTAINING
 SAFE PLACES TO LIVE AND WORK IN OUR COMMUNITY. WE ARE
 READY AND WILLING TO PROVIDE TECHNICAL ASSISTANCE IN
 UNDERSTANDING THE OFTEN COMPLEX CRITERIA THAT AFFECT
 EXISTING AND NEW HIGH RISE BUILDINGS. IT MUST BE STATED
 THAT THE SIMPLE INSTALLATION OF A HOIST-WAY
 PRESSURIZATION SYSTEM MAY BE ONE POTENTIAL METHOD TO
 ELIMINATE THE NEED FOR AN ELEVATOR LOBBY THROUGHOUT AN
 ENTIRE BUILDING. ANOTHER ALTERNATIVE IS TO INSTALL FIRE
 SHUTTERS AT THE ELEVATOR DOOR OPENINGS. THESE
 METHODOLOGIES MAY OFFER THE ADDED POTENTIAL TO INCREASE
 THE LEASABLE FLOOR AREA WITHIN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT US DIRECTLY IF WE CAN
 ASSIST YOU FURTHER IN UNDERSTANDING THESE CRITERIA AND
 HELP YOU TO ENSURE THE SAFETY OF YOUR RESIDENTS,
 TENANTS, AND PROPERTY.
  
 DOUG WISE ? 805-6650 ? [email protected]
 MIKE CARSILLO ? 804-4709 ? [email protected]
  
 FL BLDG CODE 703.2.2 SUPPLEMENTAL SHAFT AND FLOOR
 OPENING ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON
 ANY FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE
 ENCLOSURE REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO
 VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE
 FLOOR.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE NEW
 PROPOSED TENANT SPACE 801, IT APPEARS THERE MAY BE DEAD
 END CORRIDORS BEING CREATED SINCE YOU CAN NOT GO
 THROUGH ANOTHER TENANT SPACE NOT UNDER YOUR CONTROL SEE
 TENANT SEPARATION WALL BY STAIR NUMBER 2.
 2007/09 FL BLDG CODE 1014.2 EX# 3 AN EXIT ACCESS SHALL
 NOT PASS THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT
 EGRESS.
 2007/09 FL BLDG CODE 1017.3 EX 2 ALLOWS FOR 50 FEET
 MAXIMUM.
  
 4) SHEET A2 FILE ROOM # 104 DETAIL 2/ A4 INDICATES A
 WALL STOPPING JUST ABOVE THE CEILING LINE. THE FILE
 ROOM IS CONSIDERED STORAGE, THE ROOM IS APPROXIMATELY
 230 SQUARE FEET FBC-B TABLE 508.2.2.1 CONSTRUCTION.
 WHERE TABLE 508.2 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF
 RESISTING THE PASSAGE OF SMOKE. THE PARTITIONS SHALL
 EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY OR
 FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY ABOVE OR TO
 THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, OR SUB
 DECK ABOVE. DOORS SHALL BE SELF- OR AUTOMATIC CLOSING
 UPON DETECTION OF SMOKE IN ACCORDANCE WITH SECTION
 715.4.7.3.
  
 PLEASE PROVIDE COMPLIANCE WITH: FBC-B 712.6 FIRE WALLS,
 FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND
 SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  