2011-12-01 16:08:41BUILDING REVIEW COMMENTS
  
  
  
 PROVIDE WIND LOAD ANALYSIS FOR THE OPENINGS ON THE
 BUILDING. THE DOOR SPEC'S SUBMITTED ARE ONLY GOOD FOR
 -70 PSF.
  
 SUBMIT DOCUMENTION CERTIFYING A 1HR ASSEMBLY,
  
  
 LUIS MARTINEZ
 561-805-6710