| 2011-11-09 11:41:27 | | | | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- CLEARLY IDENTIFY WHICH FLAT ROOF APPROVED ASSEMBLY | | | FROM NOA SUBMITTED IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | | R301.2.1.4.3 | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | TAKE INTO CONSIDERATION THAT THIS BUILDINGIS LOCATED ON | | | EXPOSURE "C". SEC. R301.2.1.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT | | | (561)805-6712 | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|