Plan Review Notes
Plan Review Notes For Permit 11110177
Permit Number 11110177
Review Stop P
Sequence Number 2
Notes
Date Text
2011-12-27 14:09:241" WATER SUPPLY FIGURED THROUGH FLOW CHART - 60 POUNDS
 @ 1" PIPE = 47 GPM
 TABLE E103.3(3) - 70 FIXTURE UNITS REQUIRE 35 GPM = 12
 GPM RESERVE