Plan Review Notes
Plan Review Notes For Permit 11110177
Permit Number 11110177
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-01-05 13:04:142223 PALM BEACH LAKES BOULEVARD - SUITE #103
 PERMIT #11110177
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 A PLAN REVISION IS NEEDED FOR EXISTING SPRINKLER PERMIT
 #11080365. SPRINKLER VALUE HAS INCREASED WITH
 QUICK-RESPONSE SPRINKLER CONVERSION IN SUITE #101-#103.
 SPRINKLER PROTECTION TO BE PROVIDED IN NEW RESTROOM
 AREAS.
  
 A PLAN REVISION IS NEEDED FOR EXISTING FIRE ALARM
 PERMIT #11090530 TO INCLUDE THE NEW BATH AREA.
  
 SEATING NOT SECURED TO THE FLOOR SHALL BE FASTENED
 TOGTHER IN GROUPS OF AT LEAST THREE SEATS PER GROUP.
  
 ALL FIRE RATED DOORS AND FRAMING TO BE LABELED AND
 IDENTIFIED IN THE FIELD.
  
 FURTURE KITCHEN/STORAGE TO BE FIRE RATED, SELF CLOSING
 AND POSITIVE LATCHING.
  
 SEPARATE PLANS AND PERMIT WILL BE NEEDED FOR MECHANICAL
 VENTILATION OF THE RESTROOMS AND EXTERIOR FIRE LANE
 STRIPING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW