| Plan Review Notes For Permit 11110177 |
| Permit Number |
11110177 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-12-28 15:28:44 | 11110177 | | | 2223 PALM BEACH LAKES BLVD #103 | | | INTERIOR RENOVATION | | | | | | THE ELECTRICAL COMMENTS FROM THE FIRST REVIEW OF | | | NOVEMBER 15, 2011 NOTED BELOW WERE NOT ADDRESSED IN THE | | | NEW SUBMITTAL OF DECEMBER 22, 2011. | | | | | | | | | 1. PROVIDE AN ELECTRICAL RISER PLAN; LOCATE THE SERVICE | | | AND ALL PANELS ON A FLOOR PLAN; INCLUDE A SUMMARY LOAD | | | CALCULATION SHOWING EXISTING ELECTRIC SERVICE CAN | | | HANDLE THE NEW LOADS; VERIFY SAFETY CLEARANCES AND | | | ACCESS. NEC 110.26, 215.5 | | | 2. SPECIFY ON THE PLANS HOW THE NEW LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | | EXISTING BUILDING CODE 711.1 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|