Plan Review Notes
Plan Review Notes For Permit 11110177
Permit Number 11110177
Review Stop P
Sequence Number 1
Notes
Date Text
2011-11-22 14:47:18FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 IF THIS PROJECT IS A-3, THEN A UNISEX RESTROOM WILL BE
 REQUIRED. THIS RESTROOM CAN COUNT AS PART OF THE
 REQUIRED FIXTURE COUNT.
 1. FBC PLUMBING 403.7 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. THE NEW MENS ROOM REQUIRES AN ADA STALL COMPLIANT
 WITH 11-4.17.3 SIZE AND ARRANGEMENT.
 EXCEPTION (1)
 11-4.22 TOILET ROOMS.
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17
 THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
  
 3. THE WOMENS RESTROOM HAS MORE THAN 6 WATER CLOSETS SO
 IT WILL REQUIRE A STALL THAT COMPLIES WITH FIGURE
 11-4.17.3 - 36" WIDE WITH PARALLEL GRAB BARS.
 11-4.22.4 WATER CLOSETS. IF TOILET STALLS ARE PROVIDED,
 THEN AT LEAST ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH SECTION 11-4.17; WHERE SIX OR MORE
 STALLS ARE PROVIDED, IN ADDITION TO THE STALL COMPLYING
 WITH SECTION 11-4.17.3, AT LEAST ONE STALL 36 INCHES
 (915 MM) WIDE WITH AN OUTWARD SWINGING, SELF-CLOSING
 DOOR AND PARALLEL GRAB BARS COMPLYING WITH FIGURE 30(D)
 AND SECTION 11-4.26 SHALL BE PROVIDED. WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH SECTION 11-4.16. IF WATER
 CLOSETS ARE NOT IN STALLS, THEN AT LEAST ONE SHALL
 COMPLY WITH SECTION 11-4.16.
  
 3. THE FIXTURE UNIT COUNT FOR THE NEW FIXTURES SHOWN ON
 P-1 IS 71 FIXTURE UNITS. THE COLD WATER SUPPLY IS SHOWN
 AS 3/4". TABLE 603.1 REQUIRES 1 1/2" FOR 71 FU. THE
 DROP FOR THE WOMENS ROOM WOULD BE 1" FOR 45 FU.
 604.1 GENERAL. THE DESIGN OF THE WATER DISTRIBUTION
 SYSTEM SHALL CONFORM TO ACCEPTED ENGINEERING PRACTICE.
 METHODS UTILIZED TO DETERMINE PIPE SIZES SHALL BE
 APPROVED. TABLE 603.1 SHALL BE PERMITTED TO BE USED TO
 SIZE THE WATER DISTRIBUTION SYSTEM.
  
 4. WHERE THE MULTIPLE WATER CLOSETS ARE SHOWN, A DRY
 VENT BETWEEN THE TWO MOST UPSTREAM WATER CLOSETS IS
 REQUIRED
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 ***NOTE***
 IF THE PROJECT IS A-3 AND THE OCCUPANT LOAD FOR MEN IS
 1100, THE WC FIXTURE COUNT FOR MEN WOULD BE 9 ( 9 X 125
 = 1125 MEN). THE PLAN SHOWS TOTAL OF TEN WC AND
 URINALS.
 ALSO THE UNISEX RESTROOM IS PERMITTED TO BE PART OF THE
 FIXTURE COUNT FOR MEN OR WOMEN.
  