| 2011-11-14 12:05:04 | 2223 PALM BEACH LAKES BOULEVARD - SUITE #103 |
| | PERMIT #11110177 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | SCOPE: CHANGE OF USE FROM MERCANTILE TO ASSEMBLY |
| | OCCUPANCY |
| | |
| | PER NFPA 101 PLANS FOR THE EXPOSITION (SPECIAL EVENT, |
| | CONCERT, SHOW, ETC.) SHALL BE SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO THE |
| | SETTING UP ANY EVENT. THE PLANS SHALL SHOW ALL DETAILS |
| | OF THE PROPOSED EXPOSITION. NO EXPOSITION SHALL OCCUPY |
| | ANY EXPOSITION FACILITY WITHOUT APPROVED PLANS. |
| | |
| | SHEET A-1 STILL INDICATES THIS SPACE TO BE A MERCANTILE |
| | OCCUPANCY IN LIEU OF AN ASSEMBLY OCCUPANCY. |
| | |
| | SHEET A-1 INDICATES CLASS C INTERIOR WALL AND CEILING |
| | FINISHES. FOR OCCUPANT LOADS GREATER THAN 300 PERSONS, |
| | INTERIOR WALL AND CEILING FINISHES SHALL BE CLASS A OR |
| | CLASS B. |
| | |
| | THE TWO SETS OF DOUBLE EXIT DOORS (WEST WALL) NEED TO |
| | BE INCLUDED IN THE SCOPE OF WORK AND OVERALL PROJECT |
| | VALUE. SUBMIT DOOR AND HARDWARE INFORMATION. NOTE: |
| | THESE UNPERMITTED DOORS WERE RECENTLY INSTALLED AND |
| | NEED TO BE INSPECTED, TESTED AND APPROVED. |
| | |
| | THE DOUBLE EXIT DOORS (SOUTHWEST) NEED TO BE INCLUDED |
| | IN THE SCOPE OF WORK AND OVERALL PROJECT VALUE. SUBMIT |
| | DOOR AND HARDWARE INFORMATION. |
| | |
| | THE EXISTING STANDARD RESPONSE FIRE SPRINKLERS NEED TO |
| | BE REPLACED WITH QUICK RESPONSE SPRINKLERS. EXISTING |
| | SPRINKLER PERMIT #11080365 NEEDS TO HAVE SCOPE AND JOB |
| | VALUE REVISED TO REFLECT THIS CHANGE. |
| | |
| | THE OCCUPANT LOAD ON SHEET A-2 IS BASED UPON 5 SQUARE |
| | FEET PER PERSON. THE OCCUPANT LOAD SHALL NOT EXCEED ONE |
| | PERSON PER SEVEN SQUARE FEET WHEN AREAS ARE LARGER THAN |
| | 10,000 SQUARE FEET. |
| | |
| | NORTHWEST STORAGE ROOM SHALL BE PROVIDED WITH A DOOR TO |
| | SEPARATE THE STORAGE OCCUPANCY FROM THE ASSEMBLY |
| | OCCUPANCY. |
| | |
| | DEAD-END CORRIDOR (PLAN NORTH) SHALL NOT EXCEED 20 |
| | FEET. |
| | |
| | PROVIDE ADDITIONAL INFORMATION AND DETAILS FOR THE |
| | 20X30 FOOT STAGE. |
| | |
| | ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A MINIMUM |
| | OF ONE TRAINED CROWD MANAGER FOR EVERY 250 OCCUPANTS. |
| | |
| | POST PERMANENT NO SMOKING SIGNS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO |
| | RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE |
| | PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| | HARDWARE. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE |
| | DETAILS. |
| | |
| | PROVIDE EMERGENCY LIGHTING IN ALL RESTROOMS. |
| | |
| | NO ELECTRICAL WIRING PLAN SUBMITTED SHOWING POWER TO |
| | ALL EXIT SIGNS. |
| | |
| | FIRE ALARM SYSTEM SHALL BE UL (OR OTHER APPROVED |
| | AGENCY) CERTIFIED FOR CENTRAL STATION SERVICE BY FINAL |
| | FIRE INSPECTION. |
| | |
| | EXTERIOR KEY SAFE CAN BE ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | THE PAVED DRIVE TO THE WEST NEEDS TO BE MARKED AND |
| | STRIPED - FIRE LANE NO PARKING. A SEPARATE PLAN AND |
| | PERMIT IS REQUIRED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |