Plan Review Notes
Plan Review Notes For Permit 11110177
Permit Number 11110177
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-17 11:59:57BUILDING PLAN REVIEW
 PERMIT: 11110177
 ADD: 2223 PALM BEACH LAKES BLVD SUITE # 103
 CONT: LTA INC
 TEL: (561)635-8478
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THERE IS A HOLD ON THIS SUITE NUMBER, REQUIRING A
 CHANGE OF OCCUPANCY FROM MERCANTILE TO ASSEMBLY. THERE
 IS A DISCREPANCY BETWEEN SHEET A1 & A2, A1 INDICATES
 THE OCCUPANCY AS MERCANTILE (RETAIL) AND SHEET A2 AS A
 A-3 OCCUPANCY. THE ACTUAL USAGE OF THE SPACE OR
 MULTIPLE USES OF THIS SPACE MUST BE KNOWN TO ACCURATELY
 PLACE THIS TENANCY IN THE CORRECT ASSEMBLY
 SUB-GROUPING. FOR THE PURPOSE OF THIS REVIEW THE
 OCCUPANCY CLASSIFICATION WILL BE A A2 NOT THE A3 AS
 INDICATED BY THE DESIGNER OF RECORD. THERE ARE TWO
 REASONS:
  
 1A) PERMIT # 11040096 WAS FOR CONSTRUCTING A JUICE BAR
 WITHIN A MERCANTILE OCCUPANCY THE JUICE BAR HAD A
 OCCUPANCY LOAD OF LESS THAN 50 SO IT WAS STILL
 CONSIDERED RETAIL OCCUPANCY JUST AS THE FURNATURE STORE
 PORTION OF THE TENANCY, SHEET A-5 INDICATED A FURNITURE
 PLAN CONSISTENT WITH THE RETAIL OCCUPANCY. WITH THE
 DECLARED USE ON SHEET A2 OF
 A A3 OCCUPANCY WITH FOOD & DRINK THAT IS WHAT BUMPS
 THIS INTO THE A2 CATEGORY JUST AS A DANCE HALL THAT HAS
 FOOD & DRINK CONSUMPTION ON SITE.
  
 1B) CURRENTLY THE PERMIT APPLICATION APPLIED FOR IS FOR
 ONLY NEW RESTROOMS, NOT FOR A CHANGE OF USE WHICH WILL
 REQUIRE A NEW CERTIFICATE OF OCCUPANCY. THE LESSEE
 SHALL DECIDE HOW THEY WANT TO PROCEED IN GAINING CODE
 COMPLIANCE. EITHER THE CURRENT GENERAL CONTRACTOR CAN
 CHANGE THE DESCRIPTION OF WORK ON THE PERMIT
 APPLICATION UNDER THE DESCRIBE PROJECT IN DETAIL TO
 INCLUDE THE CHANGE OF OCCUPANCY AND INCLUDE THE
 ADDITIONAL WORK (INCREASED VALUE OF PROJECT) THAT WILL
 BE REQUIRED OR A SEPIRATE PERMIT CAN BE APPLIED FOR AS
 A CHANGE OF OCCUPANCY AND THE ADDITIONAL WORK THAT WILL
 BE REQUIRED UNDER THAT PERMIT. IF THE TENANT WISHES TO
 GO THE ROUTE OF A SEPARATE PERMIT FOR THE CHANGE OF
 OCCUPANCY PLEASE NOTE THE HOLD WILL NOT LET THE PERMIT
 FOR THE RESTROOMS BE ISSUED UNTIL
 THE CHANGE OF OCCUPANCY PERMIT IS ISSUED.
  
 2) ) SHEET A-2 INDICATES A NEW 20?X 30? PLATFORM BUT NO
 DESIGN CRITERIA (HEIGHT- FBC-B 410.3.1.1.) AS TO
 MATERIALS (FBC-B 410.3 / 603.1 ALLOWABLE MATERIALS),
 LIVE LOAD DESIGN & USAGE (FBC-B TABLE 1607.1),
 ACCESSIBILITY ( 11-4.1.6(1)(K)(III) VERTICAL
 ACCESSIBILITY).
  
 3) PLEASE PROVIDE A LIFE SAFETY SHEET WITH CHAIRS,
 TABLES AND OR FURNITURE LAYOUT. PLEASE PROVIDE THE
 FOLLOWING AS PART OF A MINIMUM COMMERCIAL PLAN
 REVIEW(FBC-B 106.3.5)
 3A) SITE PLAN SQUARE FOOTAGE OF THE TOTAL BUILDING
 3B) SITE PLAN ACCESSIBLE ENTRANCE AND PARKING
 3C) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS :
 COMMON PATH OF TRAVEL 1025.8/ 1025.9
 EXIT ACCESS
 EXIT
 DOORS 1025.6.1.
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 4) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING- ALARM SYSTEMS
 ASSEMBLY OCCUPANCY OVER 100 OCCUPANTS FBC-B
  
 5) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY STAGE OR PLATFORM
 TOILET AND BATHING FACILITIES PLEASE REVIEW 11-4.22.4
 WHERE 6 OR MORE TOILET STALLS ARE PROVIDED
 SPECIAL OCCUPANCY REQUIREMENTS 11-4.33 (ASSEMBLY AREAS)
 & 11-5 (RESTAURANTS & CAFETERIAS).
 PROVIDE 20% DISPROPORTIONATE COST PER FBC-B 11-4.1.6(2)
 PROVIDE IN LETTER FORM WHERE THESE FUNDS WILL BE
 IMPLEMENTED IN THE ALTERATIONS.
  
 6) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 TABLE 803.5.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  