| 2011-11-09 14:06:59 | 4000 NORTH FLAGLER DRIVE | | | PERMIT #11110147 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE GENERATOR SHALL BE PROTECTED FROM CONTACT BY THE | | | PUBLIC BY MEANS OF A FENCE OR ENCLOSURE. | | | | | | PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY | | | MATERIAL. | | | | | | CAR/VEHICLE SHALL CONTAIN LESS THAN 10 GALLONS OF FUEL. | | | VEHICLE SHALL HAVE AT LEAST ONE CABLE REMOVED FROM THE | | | BATTERY. VEHICLE SHALL NOT BE MOVED DURING THE EVENT. | | | | | | EXIT DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE | | | REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|