Plan Review Notes
Plan Review Notes For Permit 11110147
Permit Number 11110147
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-11-09 14:06:594000 NORTH FLAGLER DRIVE
 PERMIT #11110147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE GENERATOR SHALL BE PROTECTED FROM CONTACT BY THE
 PUBLIC BY MEANS OF A FENCE OR ENCLOSURE.
  
 PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY
 MATERIAL.
  
 CAR/VEHICLE SHALL CONTAIN LESS THAN 10 GALLONS OF FUEL.
 VEHICLE SHALL HAVE AT LEAST ONE CABLE REMOVED FROM THE
 BATTERY. VEHICLE SHALL NOT BE MOVED DURING THE EVENT.
  
 EXIT DOORS SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE
 REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW