| 2011-11-09 14:39:03 | 1110147 | | | 4000 N. FLAGLER DR. | | | TEMP ELECTRIC FOR TENT | | | ELECTRIC REVIEW COMMENTS | | | | | | PROVISO: | | | ALL WORK SHALL CONFORM WITH THE REQUIREMENTS OF TEH | | | NATIONAL ELECTRICAL CODE ARTICLE 590 FOR TEMPORARY | | | WIRING. | | | | | | A MAIN DISCONNECT IS REQUIRED AT THE GENERATOR | | | ALL GENERAL PURPOSE OUTLETS SHALL BE GFCI PROTECTED. | | | ALL FEEDERS AND CORDS SHALL BE PROPERLY PROTECTED | | | AGAINST PHYSICAL DAMAGE. | | | ALL LUMINARIES SHALL BE PROTECTED AGAINST PHYSICAL | | | DAMAGE. | | | OVERCURRENT PROTECTION SHALL BE PROVIDED FOR ALL | | | CIRCUITS. | | | BOXES AND PANEL BOARDS SHALL HAVE ALL UNUSED OPENINGS | | | SEALED. | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|