2011-11-09 14:39:031110147
 4000 N. FLAGLER DR.
 TEMP ELECTRIC FOR TENT
 ELECTRIC REVIEW COMMENTS
  
 PROVISO:
 ALL WORK SHALL CONFORM WITH THE REQUIREMENTS OF TEH
 NATIONAL ELECTRICAL CODE ARTICLE 590 FOR TEMPORARY
 WIRING.
  
 A MAIN DISCONNECT IS REQUIRED AT THE GENERATOR
 ALL GENERAL PURPOSE OUTLETS SHALL BE GFCI PROTECTED.
 ALL FEEDERS AND CORDS SHALL BE PROPERLY PROTECTED
 AGAINST PHYSICAL DAMAGE.
 ALL LUMINARIES SHALL BE PROTECTED AGAINST PHYSICAL
 DAMAGE.
 OVERCURRENT PROTECTION SHALL BE PROVIDED FOR ALL
 CIRCUITS.
 BOXES AND PANEL BOARDS SHALL HAVE ALL UNUSED OPENINGS
 SEALED.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  