| Notes |
| Date |
Text |
| 2011-11-15 12:27:47 | 477 SOUTH ROSEMARY AVENUEN - SUITE #221 | | | PERMIT #11110130 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE CHANGE | | | FROM RESIDENTIAL SPRINKLERS TO COMMERCIAL SPRINKLERS. | | | | | | SUBMIT CUT SHEETS FOR SPRINKLERS. | | | | | | FOR AREAS WITH EXPOSED STRUCTURE (NO CEILING) INDICATE | | | IF THE SPACE IS OBSTRUCTED OR UNOBSTRUCTED CONSTRUCTION | | | AND THE INDICATE THE DISTANCE SPRINKLERS ARE LOCATED | | | BELOW THE STRUCTURE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|