| 2011-12-19 13:39:58 | ADDITION/ALTERATION (R3) BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9N-3 |
| | FOR: |
| | A) 6'-8" FIBERGLASS DOORS AS SHOWN ON PLANS. DRAWING |
| | FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS. |
| | B) WINDOW MULLIONS. NOA 10-0819.05 WAS SUPERSEDED BY |
| | MIAMI-DADE. NEED CURRENT NOA. |
| | C) MISSING EXTERIOR DOOR NOA 06-0406.11 SPECIFIED ON |
| | ENGINEER LETTER LISTING REVIEWED PRODUCT APPROVALS. |
| | |
| | ***NOTE: PLEASE HAVE HISTORIC APPROVAL PRIOR TO |
| | SUBMITTAL TO THIS OFFICE. |
| | |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS. |
| | UPDATE LETTER STATING ALL PRODUCT APPROVALS COVERED |
| | UNDER THIS REVISION/ADDITION INCLUDING THE ONES THAT |
| | WERE SUBMITTED ON FIRST SUBMITTAL. |
| | |
| | 3- FLAT ROOF: PROVIDE RAS 117 CALCULATIONS FOR NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY |
| | GENERAL LIMITATION ON LAST PAGE OF NOA 09-0820.11 TO |
| | MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | 4- PROVIDE STORM SHUTTERS COMPLETE INSTALLATION |
| | SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE |
| | USED. THIS APPLIES TO BOTH TYPES OF SHUTTERS SUBMITTED. |
| | FABRIC SHUTTERS AND STORM PANELS. SEE CITY POLICY FOR |
| | HURRICANE SHUTTERS REQUIRED INFORMATION. |
| | |
| | 5- SPECIFY EMERGENCY OVERFLOW SCUPPERS AS REQUIRED BY |
| | SEC. R903.4.1. |
| | |
| | 7- SPECIFY HOW THE ROOF GUTTERS WILL DISCHARGE THE RAIN |
| | WATER A LEAST ONE FOOT AWAY FROM THE STRUCTURE AS |
| | REQUIRED BY SEC. R320.7. |
| | |
| | 8- ARCHITECT TO COORDINATE ROOF DRAINS WITH ENGINEER |
| | NOTE #1 ON DETAIL 1/S1. THERE ARE NOT INTERIOR ROOF |
| | DRAINS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |