| 2011-11-18 17:04:16 | ADDITION/REVISION BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PLEASE PROVIDE ENERGY CALCULATIONS AS REQUIRED BY |
| | SEC. N1100.3. |
| | |
| | 2- PLEASE PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| | REQUIRED BY DCA RULE 9N-3 FOR: |
| | A) CASEMENT WINDOWS AS SPECIFIED ON PLANS. |
| | B) SINGLE HUNG WINDOWS. NOA 11-0405.10 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE |
| | WEBSITE AND DOWNLOAD CURRENT NOA. |
| | C) FIBERGLASS EXTERIOR DOOR. FLORIDA PRODUCT APPROVAL |
| | FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS. NEED ONE FOR |
| | 6'-8" DOORS AS SPECIFIED ON PLANS. |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS, SECTIONS AND UPLIFT CONNECTOR SCHEDULE. PLEASE, |
| | PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | E) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY |
| | INDICATE SIZE OF MULLION TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| | F) FLAT ROOF. AND, CLEARLY IDENTIFY WHICH APPROVED |
| | ASSEMBLY IS GOING TO BE INSTALLED AND PROVIDE RAS 117 |
| | CALCULATIONS. CALCULATIONS TO BE SIGNED AND SEALED IF |
| | THE PRODUCT APPROVAL SUBMITTED REQUIRES IT. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR |
| | TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 4- PLEASE HAVE ALL THE REVISED PLANS AND PRODUCT |
| | APPROVALS REVIEWED BY HISTORIC FOR APPROVAL PRIOR TO |
| | SUBMITTAL TO THIS OFFICE. |
| | |
| | 5- PLEASE PROVIDE STORM SHUTTERS COMPLETE INSTALLATION |
| | SCHEDULE. AND, CLEARLY MARK ON SHUTTERS DRAWINGS |
| | SPECIFIC WALL MOUNTING CONDITIONS (EX: WALL MOUNTED |
| | SECTION 1 OR WALL MOUNTED SECTION 2, ETC.), ANCHOR TYPE |
| | AND SPACING TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES BY SEC. R301.2.1.4.3. |
| | |
| | 6- PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 7- PLEASE SPECIFY TYPE OF EXISTING BEDROOM WINDOWS TO |
| | BE REPLACED (EX: CASEMENT, SINGLE HUNG, ETC) TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310. |
| | |
| | 8- ARCHITECT TO PROVIDE HIS LICENSE NUMBER ON THE TITLE |
| | BLOCK AS REQUIRED BY SEC. 61G1-16.004 FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE. |
| | |
| | 9- VALUATION AND NUMBER OF SHEETS WERE UPDATED. OWES |
| | $692.85. |
| | |
| | 10- SPECIFY ON PLANS CARBON MONOXIDE ALARMS IN ALL |
| | BEDROOMS AS REQUIRED BY SEC. R313.4. |
| | |
| | 11- A) PLEASE SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY |
| | SEC. R903.4.1. |
| | |
| | B) ROOF SCUPPERS SHOWN ON PLANS AND ELEVATIONS DON'T |
| | SHOW ANY DOWNSPOUTS. PLEASE PROVIDE SPECIFICATIONS |
| | SHOWING HOW PROTECTING THE BUILDING AS REQUIRED BY SEC. |
| | R320.7. |
| | |
| | C) PLEASE COORDINATE ROOF DRAINS AND SCUPPERS WITH |
| | ENGINEER NOTE #1 ON DETAIL 1/S1 ON SHEET S-1. |
| | |
| | 12- PLEASE PROVIDE COMPLETE SPECIFICATIONS/DETAILS |
| | SHOWING COMPLIANCE WITH THE ROOF VENTILATION AS |
| | REQUIRED BY SEC. R806. |
| | |
| | 13- SHEET A-0: PLEASE REVISE FRAMING NOTE #9. MAXIMUM |
| | RISER HEIGHT SHALL BE 7-3/4" NO 8". SEC. R311.5.3.1 |
| | |
| | 14- SHEET A-1: PLEASE COORDINATE NEW ENTRY STEPS WITH |
| | INFORMATION SHOWN ON FOUNDATION PLAN ON SHEET S-1. AND |
| | PROVIDE RISER AND TREAD DIMENSIONS TO VERIFY COMPLIANCE |
| | WITH SEC. R311.5.3. |
| | ALSO, PROVIDE DIMENSIONS FOR STEPS AND LANDING AT REAR |
| | DOOR BY THE KITCHEN AREA AND AT THE NEW LOGGIA. |
| | |
| | 15- SHEET A-2: PLEASE CLARIFY ROOF SPECIFICATIONS ON |
| | DETAIL 1 AND DETAIL 2. INFORMATION PROVIDED IS |
| | CONFUSING THE UNDERLAYMENT WITH THE SHEATHING. CLEARLY |
| | IDENTIFY UNDERLAYMENT NAIL TYPE AND SPACING (SEE FLAT |
| | ROOF PRODUCT APPROVAL) AND ROOF SHEATHING NAIL TYPE AND |
| | SPACING. STRUCTURAL DRAWINGS ARE MISSING THE |
| | SPECIFICATIONS FOR THE ROOF SHEATHING AND THE TERRACE |
| | SHEATHING. **NOTE: SEC. R803.2.3.1 REQUIRES 8D RING |
| | SHANK NAILS AND ROOF ZONE 3 NEED TO BE AT 4"O.C.. |
| | PLEASE PROVIDE COMPLETE SPECIFICATIONS, INCLUDING THE |
| | ROOF SHEATHING THICKNESS, NAIL SIZE AND SPACING IN THE |
| | STRUCTURAL DRAWINGS. |
| | |
| | 16- SHEET S-1: A) THE SLOPE REQUIRED FOR ALL FLAT ROOFS |
| | IS 1/4" PER FOOT MINIMUM. SEC. R905.11.1. PLANS AND |
| | SECTIONS SHOW 2" SLOPE. THIS DOESN'T PROVIDE THE |
| | REQUIRED MINIMUM SLOPE. REVISE ALL SPECIFICATIONS ON |
| | PLANS AND DETAILS AS REQUIRED. |
| | |
| | B) DETAIL 1/S1 SPECIFIES 3/4" STUCCO. NEED TO PROVIDE |
| | 7/8" MIN. AS REQUIRED BY TABLE R702.1(1). PLEASE REVISE |
| | AS REQUIRED. |
| | |
| | C) PLEASE PROVIDE SPECIFICATIONS FOR COLUMNS AND |
| | HEADERS ON THE WIDENED OPENING BY THE BUTLER'S PANTRY |
| | AND THE RELOCATED BACK DOOR IN THE KITCHEN AREA. SEC. |
| | R301. |
| | |
| | D) PLEASE REVISE NOTE #1 ON DETAIL 2/S1. SEE SEC. |
| | R319.1 FOR DISTANCE FROM GRADE AND REVISE AS REQUIRED. |
| | |
| | E) PLEASE REVISE NOTE #3 ON DETAIL 2/S1. SEE SEC. R408 |
| | FOR MINIMUM REQUIREMENTS AND COORDINATE WITH |
| | ARCHITECTURAL PLANS ALSO. |
| | |
| | 17- SHEET S-2: PLEASE REVISE ALL SPECIFICATIONS ON |
| | PLANS AND DETAILS THAT REFER TO THE ROOF SLOPE. SEE |
| | ITEM 16(A) ABOVE. |
| | |
| | 18- SHEET S-3: SAME COMMENT AS #17 APPLIES. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |