| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO - SUBMIT REVISION***** |
| | |
| | THE TOTAL OCCUPANT LOAD NEEDS TO BE LESS THAN 300 |
| | PERSONS, OTHERWISE A FIRE ALARM SYSTEM IS REQUIRED AND |
| | THE MAIN ENTRANCE (DOUBLE DOORS) WOULD NEED TO BE |
| | EQUIPPED WITH PANIC HARDWARE. |
| | |
| | PROVIDE ADDITIONAL PORTABLE FIRE EXTINGUISHERS AS |
| | TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 |
| | FEET. |
| | |
| | REPEAT COMMENT: EVERY ASSEMBLY OCCUPANCY ROOM NOT |
| | HAVING FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE |
| | ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT |
| | FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| | NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | REPEAT COMMENT: PROVIDE BUILDING ADDRESS VISIBLE FROM |
| | THE STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING |
| | AND BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE |
| | AND SHALL CONTRAST THE BACKGROUND. |
| | |
| | REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED |
| | EXIT DOORS WITH EXIT SIGNS. |
| | |
| | REPEAT COMMENT: SEPARATE PLANS AND PERMITS ARE REQUIRED |
| | FOR THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM. FIRE |
| | SPRINKLER SYSTEM TO BE SUPERVISED BY A MONITORING |
| | COMPANY. SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW |
| | CEILING SPACES THAT ARE NOT CONCEALED. |
| | |
| | DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE |
| | FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE |
| | BEEN SATISFIED. |
| | |