| Plan Review Notes For Permit 11110076 |
| Permit Number |
11110076 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-12-12 11:06:21 | 11110076 | | | 1016 CLARE AVE #7 | | | INTERIOR BUILD OUT | | | | | | THE FOLLOWING ITEMS FROM THE FIRST REVIEW HAVE NOT BEEN | | | ADEQUATELY ADDRESSED. | | | | | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN | | | BATHROOMS, OUTDOORS, AND ADJACENT TO SINKS. NEC 210.8 | | | PROVIDE SPECIFICATIONS ON LIGHT FIXTURES SHOWING | | | PROTECTION AGAINST DAMAGE. LUMINAIRES SUBJECT TO | | | PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS AND | | | SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM DAMAGE. | | | NEC 410.10(E) | | | SHOW SERVICE LOCATION ON THE PLAN. NEC 230.72 | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | | NEC 110.26, 240.24, 408.17 | | | PROVIDE A MECHANISM TO GUARD THE PANEL BOARDS TO | | | PREVENT PHYSICAL DAMAGE. NEC 110.27 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|