| 2011-11-10 14:14:18 | BUILDING PLAN REVIEW |
| | PERMIT: 11110076 |
| | ADD: 1016 CLARE AVE |
| | CONT: TRI R CONSTRUCTION COMPANY |
| | TEL: (772)336-6444 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THESE ARE MINIMUMS FOR COMMERCIAL BUILDING REVIEW. |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | BUILDING: |
| | |
| | 1A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | |
| | 1B). MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | |
| | |
| | 1C) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | 1D) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| | INCLUDE THE FOLLOWING REQUIREMENTS: |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | |
| | 1E) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | DOORS AMOUNT OF OCCUPANTS ALLOWED THROUGH EGRESS |
| | DOORWAYS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS |
| | |
| | 2) PLANS SHEET A-2 DO NOT PROVIDE ENOUGH OCCUPANTS ON |
| | THE SOCCER FIELDS, ARE NOT INDICATING LINESMEN, ETC. |
| | ALONG THE SIDE LINES NO OCCUPANT LOAD HAS BEEN |
| | ESTABLISHED SEE |
| | FBC-B TABLE 1004.1.1 FOR OCCUPANT LOADS FOR SPECTATOR |
| | WAITING AND SEATING AREA BY BAR. THERE IS ANOTHER AREA |
| | TO THE RIGHT OF THE MAIN ENTRANCE APPROXIMATELY 45'X45' |
| | WITH NO DESINATION OF USAGE, NOR OCCUPANT LOAD. 106.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT INDICATE |
| | COMPLIANCE WITH 11-4.21 SHOWER STALLS NOR DRESSING |
| | ROOMS. |
| | |
| | 4) SHEET A-2 THE DOUBLE DOORS LOCATED BETWEEN THE MAIN |
| | ENTRY LOBBY AND WAITING/ SEATING AREA SWING THE WRONG |
| | WAY, WITH OCCUPANT LOADS 50 AND GREATER SWING IN THE |
| | DIRECTION OF EXIT TRAVEL, FBC-B 1008.1.2. |
| | |
| | 5) A-2) PLEASE PROVIDE ON THE LIFE SAFETY PLAN THE |
| | LOCATION FOR TABLE & CHAIRS, IF BLEACHERS WILL BE |
| | INSTALLED? IF SO OF WHAT TYPE MATERIALS? HOW HIGH OF |
| | TIERS? ACCESSIBILITY? |
| | |
| | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |