| 2011-11-17 15:30:12 | FBC 2007 PLUMBING PLAN REVIEW #1 |
| | DENIED: |
| | |
| | 1. A COFFEE LOUNGE WITH OVER 10 SEATS WOULD REQUIRE |
| | SEPERATE FACILITIES FOR MEN AND WOMEN. ALSO, A SERVICE |
| | SINK WOULD BE REQUIRED. |
| | FBC 2007 PLUMBING 403.1.1.1 |
| | |
| | 1A. FBC PLUMBING 2007 403.1.1.1 DEFINITIONS: |
| | ASSEMBLY OCCUPANCY. THE USE OF A BUILDING OR STRUCTURE, |
| | OR ANY PORTION THEREOF, FOR THE GATHERING TOGETHER OF |
| | PEOPLE FOR PURPOSES SUCH AS CIVIC, SOCIAL OR RELIGIOUS |
| | FUNCTIONS OR FOR RECREATION, OR FOR FOOD OR DRINK |
| | CONSUMPTION, OR AWAITING TRANSPORTATION. |
| | |
| | 1B......403.2 SEPARATE FACILITIES. WHERE PLUMBING |
| | FIXTURES ARE REQUIRED, SEPARATE FACILITIES SHALL BE |
| | PROVIDED FOR EACH SEX. |
| | EXCEPTIONS: |
| | 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR |
| | DWELLING UNITS AND SLEEPING UNITS. |
| | 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD |
| | SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS. |
| | 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN |
| | BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR |
| | AREA OF 3,000 SQUARE FEET (279 M2) OR LESS. |
| | |
| | 1C. FOR MORE INFORMATION PLEASE SEE DCA09-DEC-130 |
| | |
| | 2. BACKFLOW PREVENTION, ALSO A HOT AND COLD WATER |
| | DIAGRAM, INCLUDING WATER HEATER WILL BE REQUIRED. |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | PLUMBING |
| | 2. WATER SUPPLY PIPING |
| | 5. WATER HEATERS |
| | 8. BACK FLOW PREVENTION |
| | |
| | *****NOTE***** |
| | DBPR HEALTH OR OTHER MAY HAVE SEPARATE FIXTURE |
| | REQUIREMENTS |
| | DIVISION OF HOTELS AND RESTAURANTS |
| | 1940 NORTH MONROE STREET |
| | TALLAHASSEE, FL 32399-1011 |
| | |
| | PHONE: 850.487.1395 |
| | FAX: 850.921.8267 |
| | |
| | HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/FORMS/PLANREVIE |
| | WFORMS.HTML |
| | |