2011-11-07 15:03:08FBC 2007 FUEL GAS REVIEW (REVISION)
 DENIED:
  
 PIPE SIZE IS INADEQUATE PER 2007 FUEL GAS TABLE
 402.4(19). GENERATOR 250,000 BTU @ 30' WOULD REQUIRE 1"
 PIPE OR 2LB METER.
  