| 2011-11-07 15:03:08 | FBC 2007 FUEL GAS REVIEW (REVISION) | | | DENIED: | | | | | | PIPE SIZE IS INADEQUATE PER 2007 FUEL GAS TABLE | | | 402.4(19). GENERATOR 250,000 BTU @ 30' WOULD REQUIRE 1" | | | PIPE OR 2LB METER. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|