| 2011-11-02 15:50:11 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- CLEARLY IDENTIFY WHICH FLAT ROOF APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.2.1.4.3. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3. | | | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | | REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON | | | EXPOSURE "C". | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTES. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|