| Plan Review Notes For Permit 11110034 |
| Permit Number |
11110034 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-11-04 11:49:36 | 1041 45TH STREET - OAKWOOD AREA | | | PERMIT #11110034 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF | | | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. | | | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | INDICATE HOW THE EXISTING FIRE SPRINKLER SYSTEM FLOW | | | SWITCH(ES) WILL BE TIED INTO THE NEW FIRE ALARM SYSTEM. | | | | | | PLANS INDICATE THE FIRE ALARM SYSTEM WILL BE UL LISTED | | | UPON COMPLETION. UL WEBSITE DOES NOT CURRENTLY INDICATE | | | A CERTIFICATE FOR THIS LOCATION AS BEING MONITORED FOR | | | CENTRAL STATION SERVICE. PLEASE VERIFY. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|