| Date |
Text |
| 2011-11-14 13:33:58 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE 901.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A |
| | BUILDING CHANGES, THE PROVISIONS OF SECTIONS 902 |
| | THROUGH 912 SHALL APPLY. THIS INCLUDES A CHANGE OF |
| | OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A |
| | CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A |
| | DIFFERENT GROUP. |
| | |
| | 901.4 CERTIFICATE OF OCCUPANCY REQUIRED. A CERTIFICATE |
| | OF OCCUPANCY SHALL BE ISSUED WHERE A CHANGE OF |
| | OCCUPANCY OCCURS THAT RESULTS IN BEING CLASSIFIED AS A |
| | DIFFERENT OCCUPANCY CLASSIFICATION AS DETERMINED BY THE |
| | FLORIDA BUILDING CODE, BUILDING . |
| | |
| | 903.1 GENERAL. BUILDING ELEMENTS AND MATERIALS IN |
| | PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 912. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) EXISTING BUILDING CODE 905.1 GENERAL. MEANS OF |
| | EGRESS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION 912. |
| | 912.1.4 ACCESSIBILITY. ALL BUILDINGS UNDERGOING A |
| | CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| | SECTION 912.8.912.8 ACCESSIBILITY. EXISTING BUILDINGS |
| | OR PORTIONS THEREOF THAT UNDERGO A CHANGE OF GROUP OR |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 11-4.1.62(2) 2)ALTERATIONS TO AN AREA CONTAINING A |
| | PRIMARY FUNCTION.THIS SECTION INDICATES THAT 20% OR AN |
| | ADDITIONAL $9,000.00 DOLLARS SHALL BE APPLIED TO MAKING |
| | THIS STRUCTURE CODE COMPLIANT TO THE ACCESSIBILITY |
| | CODE. THE DUTY TO PROVIDE ACCESSIBLE FEATURES IS TO BE |
| | CONSIDERED IN THIS ORDER. |
| | (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE |
| | PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. |
| | (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | (I) AN ACCESSIBLE ENTRANCE; |
| | (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM: |
| | (IV) ACCESSIBLE TELEPHONES; |
| | (V) ACCESSIBLE DRINKING FOUNTAINS; AND |
| | (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH |
| | AS PARKING, STORAGE, AND ALARMS. |
| | PLEASE PROVIDE DOCUMENTATION HERE THESE MONIES WILL BE |
| | ALLOCATED. |
| | |
| | 2) SHEET 2 INDICATES AN ACCESSIBLE RAMP WHICH IS THE |
| | MEANS OF EGRESS FOR THE HANDICAPPED. THE TOP LANDING |
| | WILL NEED TO BE INCREASED IN SIZE TO MEET THE |
| | REQUIREMENTS OF 11-4.8.4(3) CHANGE OF DIRECTION AT |
| | LANDINGS. |
| | |
| | 3) SHEET 1 IN THE EXISTING DINING AREA THE FRENCH DOORS |
| | ARE TO BE FRAMED IN, SHEET 2 INDICATES 2 NEW WINDOWS ON |
| | THIS WALL, PLEASE PROVIDE PRODUCT APPROVAL FOR THESE |
| | WINDOWS. |
| | 1609, COMPONENTS AND CLADDING. PLEASE ALSO NOTE : |
| | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 4) SHEET 2 THE NEW ADA BATH IS MISSING THE REQUIRED 18" |
| | ON THE LATCH SIDE OF THE DOOR. 11-4.13.6. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |