| Plan Review Notes For Permit 11100690 |
| Permit Number |
11100690 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-29 17:18:19 | ****PROVISOS**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | ****REVISION REQUIRED PRIOR TO ELECTRICAL | | | INSPECTION**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISION REQUIRED FOR FRAME SECTION BETWEEN THE | | | EXISTING HOUSE AND PROPOSED NEW. PROVIDE ENGINEERING | | | FOR THE PROPOSED FRAME ADDITION INCLUDING ATTACHMENT TO | | | THE EXISTING STRUCTURE AND ATTACHMENT TO THE PROPOSED | | | NEW METAL STRUCTURE. | | | | | | 2. FP1, STATE WIND DESIGN CRITERIA FBC R 301.2.1. IT | | | APPEARS THAT PRESSURES STATED ARE FOR EXPOSURE B. THIS | | | PARCEL APPEARS TO BE LOCATED IN EXPOSURE C. | | | | | | 3. FP1, PLEASE REVISE ACI 318 83 REFERENCE TO CURRENT, | | | FBC R CHAPTER 43. | | | | | | 4. PLEASE DETERMINE WHICH STRUCTURAL ENGINEER IS THE | | | ENGINEER OF RECORD AND HAVE THE DELEGATED ENGINEERING | | | REVIEWED BY THE ENGINEER OF RECORD, FAC61G15-31.001. | | | | | | 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE WALL AND ROOF PANELS, STRUCTURAL COMPONENTS, FAC 9N | | | 3. | | | | | | 6. THIS PERMIT IS ISSUED AS UNINHABITABLE STORAGE | | | SPACE. | | | | | | 7. PROVIDE A STRUCTURAL DETAIL FOR THE ATTACHMENT OF | | | THE SOLAR PANELS TO SHOW HOW THEY WILL RESIST WIND | | | LOADS FBC R 301.2.1. | | | | | | 8. SMOKE ALARMS AND CARBON MONOXIDE ALARMS REQUIRED FBC | | | R313, FS553.885. | | | | | | | | | |
|