| Plan Review Notes For Permit 11100690 |
| Permit Number |
11100690 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-31 10:34:44 | ELECTRIC PLAN IS MISSING INFORMATION | | | | | | WHAT SIZE IS SYSTEM? | | | | | | NO WIRE SIZES SHOWN AT ALL | | | | | | DISCONNECT OFF MAIN WHAT SIZE | | | | | | HOW MANY MODULES ARE YOU PUTTING UP IN SERIES, | | | PARALLEL? NEED DIAGRAM OF TOTAL JOB THE SOLAR PANELS | | | (ARRAYS) | | | | | | HOW IS EACH WIRED FROM PANELS TO INVETERS | | | | | | WHAT IS EACH GROUP CAPABLE OF TOTAL VOLAGE | | | | | | MAXIMUM VOLTAGE OF SYSTEM AND MAXIMUM AMPERAGE OF EACH | | | GROUP AND TOTAL | | | | | | TYPES OF WIRES USED | | | | | | HOW ARE THEY GOING TO BE GROUNDED | | | | | | SONNY BOY 3000 IS IT LISTED? | | | | | | I DON'T SEE A COMBINER BOX | | | | | | DC DISCONNECT | | | | | | PLANS ARE SO VAGUE THERE COULD BE MORE INFORMATION | | | REQUIRED |
|