Plan Review Notes
Plan Review Notes For Permit 11100690
Permit Number 11100690
Review Stop E
Sequence Number 1
Notes
Date Text
2011-10-31 10:34:44ELECTRIC PLAN IS MISSING INFORMATION
  
 WHAT SIZE IS SYSTEM?
  
 NO WIRE SIZES SHOWN AT ALL
  
 DISCONNECT OFF MAIN WHAT SIZE
  
 HOW MANY MODULES ARE YOU PUTTING UP IN SERIES,
 PARALLEL? NEED DIAGRAM OF TOTAL JOB THE SOLAR PANELS
 (ARRAYS)
  
 HOW IS EACH WIRED FROM PANELS TO INVETERS
  
 WHAT IS EACH GROUP CAPABLE OF TOTAL VOLAGE
  
 MAXIMUM VOLTAGE OF SYSTEM AND MAXIMUM AMPERAGE OF EACH
 GROUP AND TOTAL
  
 TYPES OF WIRES USED
  
 HOW ARE THEY GOING TO BE GROUNDED
  
 SONNY BOY 3000 IS IT LISTED?
  
 I DON'T SEE A COMBINER BOX
  
 DC DISCONNECT
  
 PLANS ARE SO VAGUE THERE COULD BE MORE INFORMATION
 REQUIRED