2011-11-03 10:37:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SURVEY SHOWS STRUCTURES NOT LOCATED ON THE SURVEY.
 PLEASE INCLUDE THE FOLLOWING INFORMATION ON THE SURVEY:
 TYPE OF STRUCTURE, DISTANCE FROM STRUCTURE TO PROPOSED
 ADDITION FBC R TABLE 302.1.
  
 2. SITE PLAN SHOWS THAT THIS IS A PROPOSED ADDITION,
 WITH A FRAME SECTION BETWEEN THE EXISTING HOUSE AND
 PROPOSED NEW. PROVIDE ENGINEERING FOR THE PROPOSED
 FRAME ADDITION INCLUDING ATTACHMENT TO THE EXISTING
 STRUCTURE AND ATTACHMENT TO THE PROPOSED NEW METAL
 STRUCTURE. IF THE TWO STRUCTURES ARE NOT CONNECTED, SEE
 FBC R TABLE 302.1 REGARDING SEPARATION.
  
 3. FP1, STATE WIND DESIGN CRITERIA FBC R 301.2.1. IT
 APPEARS THAT PRESSURES STATED ARE FOR EXPOSURE B. THIS
 PARCEL APPEARS TO BE LOCATED IN EXPOSURE C.
  
 4. FP1, PLEASE REVISE ACI 318 83 REFERENCE TO CURRENT,
 FBC R CHAPTER 43.
  
 5. FP1 DOES NOT INCLUDE ANY INFORMATION FOR THE WOOD
 FRAME PORTION OF THE PROPOSED ADDITION.
  
 6. PLEASE DETERMINE WHICH STRUCTURAL ENGINEER IS THE
 ENGINEER OF RECORD AND HAVE THE DELEGATED ENGINEERING
 REVIEWED BY THE ENGINEER OF RECORD, FAC61G15-31.001.
  
 7. PLAN IS NOT CLEAR AS TO WHAT WILL BE DONE WITH THE
 OPENINGS. DOES THE SCOPE OF THIS PERMIT PROPOSE THAT
 THEY REMAIN OPEN, OR WILL DOORS/WINDOWS BE PUT IN THE
 OPENINGS?
  
 IF THEY ARE TO REMAIN OPEN, ENGINEER IS TO CONFIRM THAT
 ENCLOSED STILL APPLIES (RATHER THAN PARTIALLY
 ENCLOSED), SEE FBC R 301.2.1.1(8), FBC 1609, ASCE7-05.
  
 IF THE OPENINGS ARE TO HAVE DOORS AND WINDOWS
 INSTALLED, PROVIDE PRODUCT APPROVALS FOR THE COMPONENTS
 AND CLADDING (DOORS, WINDOWS), FAC9N 3.
  
 8. IF DOORS AND WINDOWS ARE TO BE INSTALLED, PROVIDE A
 BUCK ATTACHMENT DETAIL, FBC 106.1.
  
 9. DESIGN PRESSURES FOR ZONES 1, 2, AND 3 FOR THE ROOF
 TO BE SPECIFIED ON THE METAL BUILDING ENGINEERING, SEE
 FBC R 301.2(2) AND (3).
  
 10. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE WALL AND ROOF PANELS, STRUCTURAL COMPONENTS,
 FAC 9N 3.
  
 11. PROVIDE A DESIGNATION FOR THE PROPOSED ADDITION.
 PLANS DO NOT STATE USE OF THE ADDITION; IS THIS
 HABITABLE, STORAGE, GARAGE? PROVIDE A FLOOR PLAN
 SHOWING ALL DOORS ON THE PROPOSED ADDITION (EGRESS FOR
 THE PROPOSED ADDITION FBC106.3.5.4(5) AND SHOW HOW
 EGRESS FOR THE EXISTING BUILDING IS AFFECTED BY THE
 PROPOSED ADDITION (SHOW DOORS AND WINDOWS ON THE
 CURRENT BUILDING AFFECTED BY THE PROPOSED ADDITION,
 ROOM DESIGNATION IF APPLICABLE). PLAN IS TO INCLUDE THE
 NAME AND SIGNATURE OF THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE DESIGN, FS481, FBC106.2,
 106.3.15.
  
 HABITABLE SPACE REQUIRES ENERGY CALCS AND IMPACT FEE
 ASSESSMENT.
  
 12. DUE TO THE PROXIMITY OF THE GARAGE DOOR SIZED
 OPENINGS AND LOCATION OF THOSE DOORS IN RELATION TO THE
 DRIVEWAY, SHOW COMPLIANCE WITH FBC R 309 (GARAGE AND
 RESIDENCE SEPARATION).
  
 13. SHEET CS1 STATES THAT BUILDING USE IS BUSINESS.
 THIS WOULD BE REGULATED BY THE FLORIDA BUILDING CODE.
 PLEASE CLARIFY.
  
 14. PROVIDE A STRUCTURAL DETAIL FOR THE ATTACHMENT OF
 THE SOLAR PANELS TO SHOW HOW THEY WILL RESIST WIND
 LOADS FBC R 301.2.1.
  
 15. SMOKE ALARMS AND CARBON MONOXIDE ALARMS REQUIRED
 FBC R313, FS553.885.
  
  
  