| 2011-11-16 15:07:15 | ****PROVISOS**** |
| | ****ISSUED AT CONTRACTOR/OWNER/ARCHITECT'S RISK**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. REVISE EXPOSURE CATEGORY (TO EXPOSURE C) OR PROVIDE |
| | RATIONAL ANALYSIS FOR EXPOSURE B DESIGN, FBC1609, FBC |
| | R301.2.1.4. PROVIDE REVISED PLAN (OR LETTER) IN FIELD |
| | AT INSPECTION. |
| | |
| | 2. SITE PLAN DOES NOT APPEAR TO BE CONSISTENT WITH THE |
| | SURVEY; PLEASE VERIFY NORTH ORIENTATION. PROVIDE |
| | REVISED PLAN (OR LETTER OF CLARIFICATION) IN FIELD AT |
| | INSPECTION. |
| | |
| | 3. PROVIDE PRODUCT APPROVALS FOR THE ROOF AND DOOR, |
| | FAC9N-3. A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| | ROOF. ALTERNATIVELY, THE ROOF PRODUCT APPROVAL CAN BE |
| | SUBMITTED WITH THE ROOF PERMIT APPLICATION AND THE DOOR |
| | PRODUCT APPROVAL CAN BE SUBMITTED AS A REVISION. |
| | |
| | PROVIDE PRODUCT APPROVALS IN FIELD AT INSPECTION. |
| | |
| | 4. PLEASE REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE |
| | 704.8. |
| | |
| | PROVIDE REVISED PLAN SHOWING COMPLIANCE AT INSPECTION |
| | (OR PROVIDE INFORMATION IN LETTER FORM). |
| | |
| | 5. THE PLAN SHOWS PV PANELS ABOVE THE BENCH. WILL THIS |
| | BE ON A SEPARATE PERMIT? IF INCLUDED IN THE SCOPE OF |
| | THIS PERMIT, PROVIDE A STRUCTURAL DETAIL. |
| | |
| | PROVIDE STRUCTURAL DETAIL AT INSPECTION OR SUBMIT |
| | SEPARATE PERMIT. |
| | |
| | 6. PROVISO - FBC 11-4.1.2(2), ACCESSIBLE ROUTE |
| | REQUIRED. |
| | |
| | 7. PLEASE ALSO SEE: |
| | |
| | HTTP://WWW.ACCESS-BOARD.GOV/RECREATION/ |
| | |
| | ARCHITECT CONFIRMED THAT DESIGN COMPLIES WITH ALL |
| | REQUIREMENTS. |
| | |