2011-11-16 15:07:15****PROVISOS****
 ****ISSUED AT CONTRACTOR/OWNER/ARCHITECT'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY (TO EXPOSURE C) OR PROVIDE
 RATIONAL ANALYSIS FOR EXPOSURE B DESIGN, FBC1609, FBC
 R301.2.1.4. PROVIDE REVISED PLAN (OR LETTER) IN FIELD
 AT INSPECTION.
  
 2. SITE PLAN DOES NOT APPEAR TO BE CONSISTENT WITH THE
 SURVEY; PLEASE VERIFY NORTH ORIENTATION. PROVIDE
 REVISED PLAN (OR LETTER OF CLARIFICATION) IN FIELD AT
 INSPECTION.
  
 3. PROVIDE PRODUCT APPROVALS FOR THE ROOF AND DOOR,
 FAC9N-3. A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 ROOF. ALTERNATIVELY, THE ROOF PRODUCT APPROVAL CAN BE
 SUBMITTED WITH THE ROOF PERMIT APPLICATION AND THE DOOR
 PRODUCT APPROVAL CAN BE SUBMITTED AS A REVISION.
  
 PROVIDE PRODUCT APPROVALS IN FIELD AT INSPECTION.
  
 4. PLEASE REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE
 704.8.
  
 PROVIDE REVISED PLAN SHOWING COMPLIANCE AT INSPECTION
 (OR PROVIDE INFORMATION IN LETTER FORM).
  
 5. THE PLAN SHOWS PV PANELS ABOVE THE BENCH. WILL THIS
 BE ON A SEPARATE PERMIT? IF INCLUDED IN THE SCOPE OF
 THIS PERMIT, PROVIDE A STRUCTURAL DETAIL.
  
 PROVIDE STRUCTURAL DETAIL AT INSPECTION OR SUBMIT
 SEPARATE PERMIT.
  
 6. PROVISO - FBC 11-4.1.2(2), ACCESSIBLE ROUTE
 REQUIRED.
  
 7. PLEASE ALSO SEE:
  
 HTTP://WWW.ACCESS-BOARD.GOV/RECREATION/
  
 ARCHITECT CONFIRMED THAT DESIGN COMPLIES WITH ALL
 REQUIREMENTS.
  