| Notes |
| Date |
Text |
| 2011-11-03 11:08:37 | *****PROVISO***** | | | 1. SEPARATE IRRIGATION PERMIT REQUIRED | | | | | | 2. THE PLUMBING IS OK FOR THE CISTERN IRRIGATION | | | SYSTEM. PENDING THE ADDRESSING ISSUE (UNITY OF TITLE?) | | | | | | 3. SIGNAGE AT THE HOSE CONNECTION ON THE CISTERN SHALL | | | BE MARKED WITH THE STATEMENT "NONPOTABLE WATER. NOT FOR | | | HUMAN CONSUMPTION." | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|