| Plan Review Notes For Permit 11100682 |
| Permit Number |
11100682 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-11-07 11:23:32 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISE EXPOSURE CATEGORY (TO EXPOSURE C) OR PROVIDE | | | RATIONAL ANALYSIS FOR EXPOSURE B DESIGN, FBC1609, FBC | | | R301.2.1.4. | | | | | | 2. SITE PLAN DOES NOT APPEAR TO BE CONSISTENT WITH THE | | | SURVEY; PLEASE VERIFY NORTH ORIENTATION. | | | | | | 3. PROVIDE PRODUCT APPROVALS FOR THE ROOF AND DOOR, | | | FAC9N-3. A SEPARATE PERMIT WILL BE REQUIRED FOR THE | | | ROOF. ALTERNATIVELY, THE ROOF PRODUCT APPROVAL CAN BE | | | SUBMITTED WITH THE ROOF PERMIT APPLICATION AND THE DOOR | | | PRODUCT APPROVAL CAN BE SUBMITTED AS A REVISION. | | | | | | 4. PLEASE REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE | | | 704.8. | | | | | | 5. THE PLAN SHOWS PV PANELS ABOVE THE BENCH. WILL THIS | | | BE ON A SEPARATE PERMIT? IF INCLUDED IN THE SCOPE OF | | | THIS PERMIT, PROVIDE A STRUCTURAL DETAIL. | | | | | | 6. FBC 11-4.1.2(2), ACCESSIBLE ROUTE REQUIRED. THIS | | | WILL BE A PROVISO ITEM. | | | | | | 7. PLEASE ALSO SEE: | | | | | | HTTP://WWW.ACCESS-BOARD.GOV/RECREATION/ | | | | | | PROVIDE A LETTER WHICH CONFIRMS THAT FACILITY HAS BEEN | | | DESIGNED TO COMPLY WITH ADA REQUIREMENTS. PLEASE NOTE | | | THAT ONLY FLORIDA BUILDING CODE IS ENFORCED THROUGH | | | THIS REVIEW, AND THERE MAY BE ADDITIONAL MORE STRINGENT | | | REQUIREMENTS. | | | |
|