| 2011-10-28 13:59:58 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE ALL THE INFORMATION REQUIRED BY THE CITY |
| | POLICY FOR RE-ROOFING PERMITS: |
| | A) SPECIFY HOW MUCH ROOF AREA IS FOR FLAT ROOF AND HOW |
| | MUCH AREA IS FOR SHINGLES. |
| | |
| | B) SPECIFY ROOF MEAN ROOF HEIGHT. |
| | |
| | C) SPECIFY ROOF PITCH. |
| | |
| | 2- FLAT ROOF PRODUCT APPROVALS SUBMITTED: |
| | |
| | A) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND THE |
| | FIRST PAGES SHOWN THE GENERAL NOTES THAT APPLY. ALSO, |
| | PROVIDE PAGE SHOWING THE SPECIFIC ASSEMBLY TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1.4.3. INFORMATION SUBMITTED |
| | IS INCOMPLETE AND MIS-MATCHING UNDERLAYMENT PRODUCT |
| | APPROVAL WITH FLAT ROOF ASSEMBLIES PRODUCT APPROVAL. |
| | |
| | B) PAGE 9 OF 30 OF FLORIDA PRODUCT APPROVAL FL1654-R9 |
| | SUBMITTED INDICATES THE PROPOSED INSTALLATION SYSTEM NO |
| | W-33. THIS SYSTEM ASSEMBLY IS GOOD FOR A DESIGN |
| | PRESSURE OF -97.5 PSF. THIS IS A BONDED ROOF SYSTEM AND |
| | IT DOESN'T ALLOW NAIL ENHANCING (SEE NOTE #9 ON |
| | FL1654-R9). ACCORDING TO THE FLORIDA RESIDENTIAL CODE |
| | 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C". THE DESIGN PRESSURES FOR |
| | EXPOSURE C ARE HIGHER THAN -97.5PSF AT THE CORNER |
| | AREAS. THEREFORE, THIS SYSTEM CAN'T BE USED. NEED TO |
| | SELECT ANOTHER SYSTEM THAT MEETS THE DESIGN PRESSURES |
| | FOR EXPOSURE C. |
| | |
| | ***NOTE: MECHANICALLY ATTACHED BASE SHEET SYSTEMS |
| | ALLLOW NAIL ENHANCING CALCULATIONS. IF USING A |
| | MACHANICALLY ATTACHED SYSTEM THEN PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS AS REQUIRED BY NOTE #8 ON |
| | FLORIDA PRODUCT APPROVAL FL1654-R9. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |