| Plan Review Notes For Permit 11100668 |
| Permit Number |
11100668 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-11-16 08:59:30 | PLANS DENIED | | | 1) PAGE A-2 ON THE PLANS SHOWS UNISEX BATHROOM WITH | | | 1HR.RATED PARTITION. | | | REFER TO SECTION 607.5.3 2007 FBC(M) | | | 2) PAGE M-1 RETURN AIR IS NOT REQUIRED IN BATHROOM PER | | | SECTION 601.4 EXCEPTION 3. | | | EXHAUST IS REQUIRED PER TABLE 403.3 2007 FBC(M) . | | | 3) PLEASE PROVIDE A RETURN AIR DUCT LAYOUT ON THE | | | PLANS. | | | 4) REFER TO SECTION 602.2.1 MATERIALS EXPOSED WITHIN | | | PLENUMS 2007 FBC(M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] | | | |
|