| 2011-12-01 10:53:53 | 716 NORTH SAPODILLA AVENUE |
| | PERMIT #11100668 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. |
| | |
| | STORAGE OCCUPANCIES SHALL BE SEPARATED FROM MERCANTILE |
| | OCCUPANCIES WITH A 2-HOUR FIRE RATED BARRIER. ALL |
| | OPENINGS AND PENETRATIONS SHALL BE PROTECTED. |
| | |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. |
| | |
| | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, |
| | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE. THE LOCK/LATCH RELEASING MECHANISM ON ALL |
| | DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE |
| | RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE |
| | AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| | UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| | SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| | SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| | TWISTING OF THE WRIST TO OPERATE. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | NOTE: ONLY ONE EXIT DOOR IS REQUIRED FOR CLASS C |
| | MERCANTILE OCCUPANCIES HAVING A COMMON PATH OF TRAVEL |
| | OF 75 FEET OR LESS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |