| 2011-11-03 10:46:55 | 517 CLEMATIS STREET |
| | PERMIT #11100660 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. |
| | |
| | CONFIRM ONE EMERGENCY LIGHT FIXTURE IN DINING #102 WILL |
| | PROVIDE ONE FOOT CANDLE OF LIGHT AT THE FLOOR ALONG THE |
| | EGRESS PATH. |
| | |
| | GAS-FIRED PIZZA OVEN DOES NOT APPEAR TO BE LOCATED |
| | BELOW THE COMMERCIAL COOKING HOOD. |
| | |
| | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| | SURFACE. |
| | |
| | ASSEMBLY ROOM SHALL HAVE THE OCCUPANT LOAD OF THE ROOM |
| | POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM |
| | THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| | NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | VERIFY EXISTING EXIT DOOR LOCK/LATCH RELEASING |
| | MECHANISMS. NOTE: A THUMB TURN LOCK IS NOT PERMITTED ON |
| | EXIT DOORS. THE MAIN ENTRY IS PERMITTED TO BE EQUIPPED |
| | WITH A KEYED LOCK WITH LOCK/UNLOCK INDICATOR WINDOW AND |
| | SIGNAGE STATING THE DOOR IS TO REMAIN UNLOCKED DURING |
| | BUSINESS HOURS. NO OTHER LOCKING OR LATCHING MECHANISMS |
| | ARE PERMITTED. |
| | |
| | SEPARATE PLANS AND PERMIT REQUIRED FOR COMMERCIAL HOOD |
| | AND KITCHEN HOOD SUPPRESSION SYSTEM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |