| 2012-01-03 13:56:27 | 222 LAKEVIEW AVENUE - 8TH FLOOR | | | PERMIT #11100656 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE VISUAL FIRE ALARM NOTIFICATION APPLIANCES IN | | | FILE ROOM #818 AND PANTRY ROOM #802. | | | | | | REPEAT COMMENT: SHEET FP2: FOR SYSTEM PRESSURES | | | EXCEEDING 100 PSI, ARMOVERS AND END OF BRANCH LINE | | | PENDENT SPRINKLERS SHALL BE PROTECTED FROM UPWARD | | | MOVEMENT. HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF | | | THE DROP ELBOW. INDICATE THE HANGER TYPE OR METHOD TO | | | BE USED FOR RESTRAINING UPWARD MOVEMENT. (NOTE: THE | | | HINGED-SPLIT RING HANGER ON FP2 IS NOT LISTED FOR FIRE | | | PROTECTION USE.) | | | | | | REPEAT COMMENT: SHEET FP2: PER NFPA 13, PIPING SHALL BE | | | HYDROSTATICALLY TESTED AT 50 PSI ABOVE STATIC PRESSURE | | | IN EXCESS OF 150 PSI. THIS BUILDING HAS A 1500 GPM FIRE | | | PUMP THAT PRODUCES 165 PSI AT CHURN. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|