Plan Review Notes
Plan Review Notes For Permit 11100656
Permit Number 11100656
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2012-01-03 13:56:27222 LAKEVIEW AVENUE - 8TH FLOOR
 PERMIT #11100656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE VISUAL FIRE ALARM NOTIFICATION APPLIANCES IN
 FILE ROOM #818 AND PANTRY ROOM #802.
  
 REPEAT COMMENT: SHEET FP2: FOR SYSTEM PRESSURES
 EXCEEDING 100 PSI, ARMOVERS AND END OF BRANCH LINE
 PENDENT SPRINKLERS SHALL BE PROTECTED FROM UPWARD
 MOVEMENT. HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF
 THE DROP ELBOW. INDICATE THE HANGER TYPE OR METHOD TO
 BE USED FOR RESTRAINING UPWARD MOVEMENT. (NOTE: THE
 HINGED-SPLIT RING HANGER ON FP2 IS NOT LISTED FOR FIRE
 PROTECTION USE.)
  
 REPEAT COMMENT: SHEET FP2: PER NFPA 13, PIPING SHALL BE
 HYDROSTATICALLY TESTED AT 50 PSI ABOVE STATIC PRESSURE
 IN EXCESS OF 150 PSI. THIS BUILDING HAS A 1500 GPM FIRE
 PUMP THAT PRODUCES 165 PSI AT CHURN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW