2011-12-05 11:18:53222 LAKEVIEW AVENUE - 8TH FLOOR
 PERMIT #11100656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: NO FIRE ALARM ENGINEERING DOCUMENTS
 SUBMITTED.
  
 REPEAT COMMENT: SHEET FP2: FOR SYSTEM PRESSURES
 EXCEEDING 100 PSI, ARMOVERS AND END OF BRANCH LINE
 PENDENT SPRINKLERS SHALL BE PROTECTED FROM UPWARD
 MOVEMENT. HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF
 THE DROP ELBOW. INDICATE THE HANGER TYPE OR METHOD TO
 BE USED FOR RESTRAINING UPWARD MOVEMENT. (NOTE: THE
 HINGED-SPLIT RING HANGER ON FP2 IS NOT LISTED FOR FIRE
 PROTECTION USE.)
  
 REPEAT COMMENT: SHEET FP2: PER NFPA 13, PIPING SHALL BE
 HYDROSTATICALLY TESTED AT 50 PSI ABOVE STATIC PRESSURE
 IN EXCESS OF 150 PSI. THIS BUILDING HAS A 1500 GPM FIRE
 PUMP THAT PRODUCES 165 PSI AT CHURN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW