2011-11-02 09:55:30222 LAKEVIEW AVENUE - 8TH FLOOR
 PERMIT #11100656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE
 SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE - NFPA
 101.
  
 NO FIRE ALARM ENGINEERING DOCUMENTS SUBMITTED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION/MODIFICATION OF THE FIRE SPRINKLER SYSTEM,
 FIRE ALARM SYSTEM AND ACCESS CONTROL SYSTEM.
  
 SHEET A103: THE MANUAL PUSH TO EXIT BUTTON FOR THE MAIN
 ENTRY MAGNETIC DOOR LOCKS ARE REQUIRED TO BE LOCATED
 WITHIN 60-INCHES (HORIZONTALLY) OF THE DOOR LEVER.
  
 SHEET A103: CONFIRM THE SECONDARY EXIT DOOR LOCATED AT
 CORRIDOR 816 IS EQUIPPED WITH AN ELECTRIFIED HINGE AND
 NOT A MAGNETIC LOCK (WITH PUSH TO EXIT BUTTON).
  
 SHEET A106: THE FABRIC WALLCOVERINGS SHALL MEET THE
 SMOKE DEVELOPMENT (0-450) AND FLAME SPREAD (76-200)
 REQUIREMENTS FOR CLASS C INTERIOR FINISHES PER NFPA
 101.
  
 SHEET FP2: FOR SYSTEM PRESSURES EXCEEDING 100 PSI,
 ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS
 SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL
 BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 SHEET FP2: PER NFPA 13, PIPING SHALL BE HYDROSTATICALLY
 TESTED AT 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150
 PSI. THIS BUILDING HAS A 1500 GPM FIRE PUMP THAT
 PRODUCES 165 PSI AT CHURN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  