| 2011-11-02 09:55:30 | 222 LAKEVIEW AVENUE - 8TH FLOOR |
| | PERMIT #11100656 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA |
| | FIRE PREVENTION CODE - NFPA 101. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE |
| | SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE - NFPA |
| | 101. |
| | |
| | NO FIRE ALARM ENGINEERING DOCUMENTS SUBMITTED. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION/MODIFICATION OF THE FIRE SPRINKLER SYSTEM, |
| | FIRE ALARM SYSTEM AND ACCESS CONTROL SYSTEM. |
| | |
| | SHEET A103: THE MANUAL PUSH TO EXIT BUTTON FOR THE MAIN |
| | ENTRY MAGNETIC DOOR LOCKS ARE REQUIRED TO BE LOCATED |
| | WITHIN 60-INCHES (HORIZONTALLY) OF THE DOOR LEVER. |
| | |
| | SHEET A103: CONFIRM THE SECONDARY EXIT DOOR LOCATED AT |
| | CORRIDOR 816 IS EQUIPPED WITH AN ELECTRIFIED HINGE AND |
| | NOT A MAGNETIC LOCK (WITH PUSH TO EXIT BUTTON). |
| | |
| | SHEET A106: THE FABRIC WALLCOVERINGS SHALL MEET THE |
| | SMOKE DEVELOPMENT (0-450) AND FLAME SPREAD (76-200) |
| | REQUIREMENTS FOR CLASS C INTERIOR FINISHES PER NFPA |
| | 101. |
| | |
| | SHEET FP2: FOR SYSTEM PRESSURES EXCEEDING 100 PSI, |
| | ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS |
| | SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL |
| | BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE |
| | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING |
| | UPWARD MOVEMENT. |
| | |
| | SHEET FP2: PER NFPA 13, PIPING SHALL BE HYDROSTATICALLY |
| | TESTED AT 50 PSI ABOVE STATIC PRESSURE IN EXCESS OF 150 |
| | PSI. THIS BUILDING HAS A 1500 GPM FIRE PUMP THAT |
| | PRODUCES 165 PSI AT CHURN. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |