2011-10-28 15:52:13BUILDING PLAN REVIEW
 PERMIT: 11100646
 ADD: 1009 BANYAN BLVD
 CONT: KIRMS COMMUNICATIONS
 TEL: (561)577-8827
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) TOWER HISTORY INDICATES THE TOWER BEING BUILT IN
 1989 UNDER THE STANDARD BUILDING CODE (CORRECTION) NOT
 THE SOTHERN STANDARD BUILDING CODE AND THE WIND LOADING
 WAS
 110 MPH FASTEST MILE NOT 120 MPH FASTEST MILE. PLEASE
 MAKE THESE CORECTIONS.
  
 1B) THE SECOND ISSUE IS UNDER THE HEADING 4.0 CURRENT
 WIND LOAD REQUIREMENTS. WOULD BE THE 2007/09 FLORIDA
 BUILDING CODE AND WIND ZONE IS 140 MPH 3 SECOND GUST.
 ASCE 7- 05 NOT THE ASCE-98 AND THE REFRENCED STANDARD
 FOR BROADCAST STRUCTURES IS ANSI/TIA?EIA-222-G. PLEASE
 BE AWARE THAT THE EXPOSURE CATEGORY FOR THIS AREA IS A
 "C" EXPOSURE, THESE CHANGES IN THE WIND DESIGN WILL
 CHANGE THE LOAD ASSUMPTIONS THAT WERE SUBMITTED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER