| Notes |
| Date |
Text |
| 2011-10-28 15:52:13 | BUILDING PLAN REVIEW | | | PERMIT: 11100646 | | | ADD: 1009 BANYAN BLVD | | | CONT: KIRMS COMMUNICATIONS | | | TEL: (561)577-8827 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1A) TOWER HISTORY INDICATES THE TOWER BEING BUILT IN | | | 1989 UNDER THE STANDARD BUILDING CODE (CORRECTION) NOT | | | THE SOTHERN STANDARD BUILDING CODE AND THE WIND LOADING | | | WAS | | | 110 MPH FASTEST MILE NOT 120 MPH FASTEST MILE. PLEASE | | | MAKE THESE CORECTIONS. | | | | | | 1B) THE SECOND ISSUE IS UNDER THE HEADING 4.0 CURRENT | | | WIND LOAD REQUIREMENTS. WOULD BE THE 2007/09 FLORIDA | | | BUILDING CODE AND WIND ZONE IS 140 MPH 3 SECOND GUST. | | | ASCE 7- 05 NOT THE ASCE-98 AND THE REFRENCED STANDARD | | | FOR BROADCAST STRUCTURES IS ANSI/TIA?EIA-222-G. PLEASE | | | BE AWARE THAT THE EXPOSURE CATEGORY FOR THIS AREA IS A | | | "C" EXPOSURE, THESE CHANGES IN THE WIND DESIGN WILL | | | CHANGE THE LOAD ASSUMPTIONS THAT WERE SUBMITTED. | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|