| Plan Review Notes For Permit 11100591 |
| Permit Number |
11100591 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-27 15:02:12 | 531 CLEMATIS STREET | | | PERMIT #11100591 | | | UP 10/28 DN 10/31 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | | | | | | | | | | |
|