2011-11-15 09:47:202007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLANS SPECIFY A 2 HP JANDY STEALTH POOL PUMP AND
 THE MANUFACTURER'S SPECIFICATION HAS THE SINGLE SPEED
 2HP, MODEL SHPF2.0 CIRCLED. HOWEVER, THE PUMP CURVE
 THAT WAS MARKED 90 GPM @ 56' TDH IS FOR A 1HP SINGLE
 SPEED PUMP, MODEL SHPF1.0. THE 2HP PUMP HAS A FLOW RATE
 OF OVER 130 GPM @ 56' TDH, WHICH GIVES A VELOCITY OF
 8.48 FT/SEC IN THE 2-1/2" BRANCH PIPING AND EXCEEDS THE
 MAXIMUM WATER VELOCITY OF 6 FT/SEC ALLOWED BY FBC
 R4101.6.3. PLEASE CORRECT.
  
 2) SUBMIT TWO COPIES OF THE TOTAL DYNAMIC HEAD
 CALCULATIONS SHOWING HOW THE 56 FEET OF TDH WAS
 DETERMINED. FBC R4101.6.1
  
 ROBERT MCDOUGAL