| Plan Review Notes For Permit 11100547 |
| Permit Number |
11100547 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-01 09:56:24 | RE-ROOF SUBMITTAL FOR ALTERNATIVE MATERIALS AND METHODS | | | BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | | | | | | | ALTERNATIVE MATERIALS AND METHODS INSTALLATION IS | | | APPROVED BY ROBERT BROWN (ASSISTANT BUILDING OFFICIAL). | | | THE FOLLOWING INFORMATION IS REQUIRED BY HIM TO APPROVE | | | PROPOSED INSTALLATION: IF YOU HAVE ANY QUESTIONS, | | | PLEASE CALL ROBERT BROWN AT (561)805-6652. | | | | | | 1- TABLE 3 OF TILE NOA 07-0914.13 HAS 3:12 MIN. SLOPE. | | | EXISTING ROOF IS 2:12 SLOPE. ENGINEER IS USING THE | | | RESTORING MOMENT FOR A 3:12 PITCH. ENGINEER TO PROVIDE | | | CALCULATIONS SHOWING HOW OBTAINING THE RESTORING MOMENT | | | FOR A 2:12 PITCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC. | | | | | | | | | 2- NEED TO SHOW COMPATIBILITY OF AH160 FOAM WITH THE | | | SELECTED FLAT ROOF SYSTEM CAP SHEET. NEED | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS OR OTHER | | | JUSTIFICATION FOR COMPATIBILITY. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|