| Plan Review Notes For Permit 11100547 |
| Permit Number |
11100547 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-26 13:25:26 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- CLAY TILE CAN'T BE INSTALLED IN 2:12 ROOF PITCH. | | | SEC. R905.3.2 AND FRSA/TRI 07320. | | | NEED PRODUCT APPROVAL FOR ROOF TYPE THAT CAN BE | | | INSTALLED ON EXISTING ROOF SLOPE. | | | | | | 2- CLARIFY WHY RE-ROOFING THE REAR PATIO ROOF ONLY. | | | NEED TO VERIFY COMPLIANCE WITH SEC. 611 OF 2007 | | | FBC-EXISTING BUILDING. ENTIRE HOUSE MAY NEED TO BE | | | RE-ROOFED. | | | ***NOTE: IF COMPLETE HOUSE RE-ROOF IS REQUIRED, THEN | | | THE ROOF TO WALL CONNECTIONS SECTION NEED TO BE | | | ADDRESSED ALSO. HOUSE VALUE IS MORE THAN #300,000. SEC. | | | 611.8 EXISTING BUILDING CODE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|