| Plan Review Notes For Permit 11100546 |
| Permit Number |
11100546 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-07 08:51:37 | 11100546 | | | 429 BELEVEDERE RD | | | ELECTRICAL SERVICE WORK | | | | | | VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | | CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE | | | EQUIPMENT. NEC 110.9 | | | VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND | | | CLEARANCE. NEC 230.24 | | | INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER. | | | NEC 310.16 | | | VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN | | | ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC | | | 230.72 | | | SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|