Date Text
2011-10-21 08:48:02RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- CLEARLY SPECIFY WHICH APPROVED FLAT ROOF ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC.
  
 2- SPECIFY HOW IS THE ROOF TILE GOING TO BE INSTALLED.
 ADHESIVE OR SCREWS/NAILS. TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC.
  
 ***NOTE: PROVIDE CALCULATIONS SHOWING THE REQUIRED
 DESIGN PRESSURES AND THE REQUIRED ATTACHMENT RESISTANCE
 EXPRESSED AS A MOMENT - MF(FT-LBF). SEE NOA SUBMITTED.
 TAKE INTO CONSIDERATION THAT THIS BUILDING IS LOCATED
 ON EXPOSURE "C".
  
 3- IF USING ADHESIVE TO INTALL ROOF TILES, THEN PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3. SEE ROOF
 TILE NOA FOR LISTED ADHESIVES AND CORRESPONDING UPLIFT
 MOMENT.
  
 4- CLARIFY WHERE IS THE UNDERLAYMENT SHOWN ON NOA
 11-0113.14 GOING TO BE INSTALLED. IS THIS FOR THE FLAT
 ROOF OR PITCHED ROOF? AND WHY?.
  
 5- SPECIFY BUILDING MEAN ROOF HEIGHT TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 FBC.
  
 6- FOR INFORMATION ONLY: A) ANY ROOF EQUIPMENT REMOVAL
 REQUIRES SEPARATE PERMIT.
  
 B) ANY ROOF DRAINS RETROFIT REQUIRE PLUMBING REVIEW.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712